2016-10-13 08:48:56 | 1) NOTE #1 IN THE SANITARY NOTES STATE THAT THE |
| EXISTING UNDERGROUND CAST IRON IS GOING TO BE |
| REPLACED.INDICATE ON THE PLAN HOW THE PIPNG WILL BE |
| ACCESSED. WILL THE SLAB BE CUT OR WILL THERE BE |
| TUNNELING UNDER THE SLAB? IF TUNNELING WILL BE DONE THE |
| FOLLOWING INFORMATION SHALL BE SUBMITTED. |
| PLUMBING REPAIR TUNNEL WORK |
| 2) SHOW HOW THE NEW PIPE WILL BE SUPPORTED, THE TYPE OF |
| ADAPTERS USED FOR THE CONNECTIONS TO EXISTING PIPE, AND |
| THE LOCATIONS OF REQUIRED CLEANOUTS. DETAILS AND |
| BACKFILLING PROCEDURES SHALL BE SUBMITTED THAT CLEARLY |
| SHOW HOW THE STRUCTURAL INTEGRITY OF THE CONCRETE SLAB |
| WILL BE MAINTAINED DURING EXCAVATION AND BACKFILLING. |
| STRUCTURAL FOAM IS NOT PERMITTED FOR BACKFILL BELOW |
| GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| SECTION 318.8 AND THE FLORIDA BUILDING CODE, BUILDING, |
| SECTION 2603.9. |
| 3) SUBMIT A SLAB REPAIR DETAIL IF THE SLAB WILL BE CUT |
| TO ACCESS THE PIPE.SHOW THE WIDTH OF THE REPAIR AREA, |
| THE SIZE OF THE DOWELS TO BE INSTALLED, THE EMBEDMENT |
| DEPTH OF THE DOWELS INTO THE EXISTING AND THE NEW SLAB |
| REPAIR, THE SPACING OF THE DOWELS, AND THE ANCHORING |
| METHOD OF THE DOWELS INTO THE EXISTING SLAB. |
| 4) THE DRINKING FOUNTAIN,THE HANDICAP LAVATORY AND THE |
| JANITOR SINK ARE ALL DRAWN ON THE RISER AS BEING FLOOR |
| MOUNTED FIXTURES AND WOULD BE S- TRAPPED. THESE SHOULD |
| BE DRAWN AS STACKED AND VENTED FIXTURES. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |