Plan Review Notes For Permit 16100098 |
Permit Number |
16100098 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-11 07:50:15 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | 9N-3. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR | | NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND | | MAXIMUM DESIGN PRESSURES FOR THE ROOFING MATERIALS. | | | | 2) SUBMIT TWO SETS OF SIGNED AND SEALED WINDLOAD DATA | | WITH REQUIRED COMPONENT AND CLADDING PRESSURES FOR THE | | PROJECT. FBC 107.2.1 & 107.2.1.3 | | | | 3) SUBMIT TWO SETS OF ANY OTHER DOCUMENTS THAT ARE | | REQUIRED BY THE PRODUCT APPROVALS OR ROOFING STANDARDS, | | SUCH AS, MOISTURE TESTS FOR THE INSULATION ABOVE THE | | ROOF DECK. FBC 107.2.1 |
|