2016-10-19 14:02:42 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| |
| DEFICIENT APPLICATION |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| |
| 1. ELECTRICAL PERMIT REQUIRED - E3901.2 |
| 2. MECHANICAL PERMIT REQUIRED - FBC1204.1 |
| 3. DESIGNER TO SIGN PLANS |
| 4. PROVIDE SITE PLAN. IDENTIFY LOCATIO0N AND ELEVATION |
| OF STRUCTURE |
| 5. PROVIDE FRAMING DETAILS FOR OPENINGS |
| 6. PROVIDE DESIGN WIND LOADS FOR OPENINGS |
| |
| E3901.2 GENERAL PURPOSE RECEPTACLE DISTRIBUTION. |
| IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING |
| ROOM, PARLOR, LIBRARY, DEN, SUN ROOM, BEDROOM, |
| RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING |
| UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN |
| SECTIONS E3901.2.1 THROUGH E3901.2.3 (SEE FIGURE |
| E3901.2). |
| |
| 1204.1 EQUIPMENT AND SYSTEMS. |
| INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE |
| PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS |
| CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT |
| LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) ABOVE |
| THE FLOOR ON THE DESIGN HEATING DAY. |
| |
| FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| |
| FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| |
| FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |