2016-10-04 14:19:381ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100040
 10/4/16
  
 1) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 INSTALLATION OF THE ROOF TOP MECHANCIAL EQUIPMENT PER
 SECTION 301.15. PROVIDE COMPLETE DETAILS AND DESIGN
 CRITERIA PER SECTION 1609 FBC-14 BULDING:
  
 WIND DESIGN CRITERIA
 2014P FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 5) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2).
  
 2) ADVISORY: THE REQUIRED ATTACHMENTS TO THE PRIVATE
 PROVIDER NOTICE WERE NOT PROVIDED AS REQUIRED: 1.
 QUALIFICATION STATEMENTS AND/OR RESUMES OF THE PROVATE
 PROVIDER AND ALL DULY AUTHORIZED RESIDENTS. 2) PROOF OF
 INSURANCE FOR PROFESSIONAL AND COMPREHENSIVE LIABILIY
 PER FLORIDA STAUTES SECTION 553.791(16). 3) NAME AND
 LICENSE NUMBER OF THE INSPECTOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  