2016-10-04 14:19:38 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #16100040 |
| 10/4/16 |
| |
| 1) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR |
| INSTALLATION OF THE ROOF TOP MECHANCIAL EQUIPMENT PER |
| SECTION 301.15. PROVIDE COMPLETE DETAILS AND DESIGN |
| CRITERIA PER SECTION 1609 FBC-14 BULDING: |
| |
| WIND DESIGN CRITERIA |
| 2014P FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| 5) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE |
| TABLE 1609.2(2). |
| |
| 2) ADVISORY: THE REQUIRED ATTACHMENTS TO THE PRIVATE |
| PROVIDER NOTICE WERE NOT PROVIDED AS REQUIRED: 1. |
| QUALIFICATION STATEMENTS AND/OR RESUMES OF THE PROVATE |
| PROVIDER AND ALL DULY AUTHORIZED RESIDENTS. 2) PROOF OF |
| INSURANCE FOR PROFESSIONAL AND COMPREHENSIVE LIABILIY |
| PER FLORIDA STAUTES SECTION 553.791(16). 3) NAME AND |
| LICENSE NUMBER OF THE INSPECTOR. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |