2018-05-11 14:17:243RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100030
 5/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED, ALL OF THE SMOKE CONTROL FANS
 MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER
 SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL
 RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E
 (SEE FANS- PAGE 21). THE LETTER FROM TOM BARROW COMPANY
 TO KAST CONSTRUCTION THAT WAS SUBMITTED TO THE BUILDING
 DEPARTMENT STATES THAT ALL OF THE SMOKE CONTROL FANS
  
 ARE UL LISTED AND LABELED FOR SMOKE CONTROL, HOWEVER
 THIS IS NOT THE ISSUE IN DISPUTE. THE ISSUE IS THE
 LETTER ALSO STATES THAT THE SMOKE CONTROL FANS GEF-1-1,
 GEF-1-2, SEF-1-1, LPF-1-1, SPF-1-1, SPF-R-1, AND
 SPF-R-2 ARE EQUIPPED WITH 1 BELT ONLY, AND THEREFORE
 ARE NON-COMPLIANT. DUE TO THE FACT THAT THIS IS THE 3RD
 REVIEW OF THE PROJECT, THE ISSUE WAS REFERRED TO ROBERT
 BROWN
  
 BUILDING OFFICIAL FOR WPB. HIS JUDGEMENT IS THAT THE
 TWO-BELT MINIMUM REQUIREMENT WILLL BE ENFORCED. AS A
 RESULT THESE COMMENTS HAVE BEEN WRITTEN, AND A PHONE
 CALL WAS PLACED TO TWR ENGINEERS TO ALERT THEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  