Plan Review Notes For Permit 16100030 |
Permit Number |
16100030 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-07-21 11:32:13 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16100030 | | 7/21/2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) AS PREVIOUSLY NOTED, THE LOREN COOK QMX AND CPS FANS | | MUST BE EQUIPPED WITH A MINIMUM OF TWO BELTS PER | | SECTION 909.10.5. FBC-10, AND THE SMOKE CONTROL | | RATIONAL ANALYSIS FOR THE PROJECT BY JOSEPH E. HAUF P.E | | (SEE FANS- PAGE 21). ADDITIONALLY, PLEASE PROVIDE | | VERIFICATION THAT THE FANS BEAR THE UL LISTING AND | | LABELING AS POWER VENTILATORS FOR SMOKE CONTROL | | SYSTEMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|