2016-10-13 10:47:41 | 1ST REVIEW FBC-2014 MECHANICAL |
| MASTER #15031312 |
| REVISION #16100030 |
| 333 DOWNTOWN |
| 10/13/16 |
| |
| 1) BELT-DRIVEN SMOKE CONTROL FANS ARE REQUIRED TO HAVE |
| A MINIMUM OF TWO BELTS PER SECTION 513.10.5. THE |
| SUBMITTALS DO NOT INDICATE COMPLAINCE, HOWEVER THE |
| EMAIL FROM KAST CONSTRUCTION INDICATES THAT FANS- |
| LPF-1, SPF-R-1-1, AND SPF-R-2-1 EACH HAVE ONLY ONE |
| BELT. (SEE COPIED EMAIL BELOW COMMENT #3). |
| |
| 2) PROVIDE A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA |
| FOR THE COOK SHUTTER. |
| |
| 3) THE FAN SCHEDULE ON APPROVED SHEET M4.01A MUST BE |
| REVISED TO MATCH THE FANS SELECTED FOR USE ON THE |
| PROJECT. |
| |
| |
| MATT STILL, SENIOR PROJECT MANAGER |
| PHONE 561-689-2910 |
| CELL 561-603-9031 |
| FAX 561-689-2911 |
| EMAIL [email protected] |
| 701 NORTHPOINT PARKWAY, SUITE 400 |
| WEST PALM BEACH, FL 33407 |
| WWW.KASTBUILD.COM |
| |
| FROM: WALKER, JIM [MAILTO:[email protected]] |
| SENT: THURSDAY, OCTOBER 06, 2016 2:13 PM |
| TO: MATT STILL ; FRANK WYNES |
| |
| SUBJECT: RE: 333 DOWNTOWN |
| |
| MATT AND FRANK, |
| |
| HERE IS THE ANSWER. IF THEY ARE REVIEWING THE SMOKE |
| CONTROL FANS WITH UL RATING THAT WE HAVE UNDER |
| SUBMITTAL RIGHT NOW, HERE IS THE BELT COUNT. |
| |
| LPF-1 GROOVE DRIVE ? 1 BELT |
| SPF-1-1 2 GROOVE DRIVE ? 2 BELTS |
| SPF1-2 2 GROOVE DRIVE ? 2 BELTS |
| SPF-R-1 1 GROOVE DRIVE -1 BELT |
| SPF-R-2 1 GROOVE DRIVE ? 1 BELT |
| |
| |
| LET ME KNOW IF I CAN BE OF MORE ASSISTANCE. |
| |
| THANKS, |
| |
| BEST REGARDS, |
| |
| JIM WALKER |
| SALES ENGINEER |
| |
| ** SEND QUOTE REQUESTS TO [email protected] |
| ** CC TO ME [email protected] |
| |
| TOM BARROW COMPANY - TAMPA |
| OFFICE: 813-888-9000 EXT. 223 |
| MOBILE: 813-401-6755 |
| WWW.TOMBARROW.COM |
| AIR COOLED CHILLERS IN STOCK |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |