2016-10-13 10:47:411ST REVIEW FBC-2014 MECHANICAL
 MASTER #15031312
 REVISION #16100030
 333 DOWNTOWN
 10/13/16
  
 1) BELT-DRIVEN SMOKE CONTROL FANS ARE REQUIRED TO HAVE
 A MINIMUM OF TWO BELTS PER SECTION 513.10.5. THE
 SUBMITTALS DO NOT INDICATE COMPLAINCE, HOWEVER THE
 EMAIL FROM KAST CONSTRUCTION INDICATES THAT FANS-
 LPF-1, SPF-R-1-1, AND SPF-R-2-1 EACH HAVE ONLY ONE
 BELT. (SEE COPIED EMAIL BELOW COMMENT #3).
  
 2) PROVIDE A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA
 FOR THE COOK SHUTTER.
  
 3) THE FAN SCHEDULE ON APPROVED SHEET M4.01A MUST BE
 REVISED TO MATCH THE FANS SELECTED FOR USE ON THE
 PROJECT.
  
  
 MATT STILL, SENIOR PROJECT MANAGER
 PHONE 561-689-2910
 CELL 561-603-9031
 FAX 561-689-2911
 EMAIL [email protected]
 701 NORTHPOINT PARKWAY, SUITE 400
 WEST PALM BEACH, FL 33407
 WWW.KASTBUILD.COM
  
 FROM: WALKER, JIM [MAILTO:[email protected]]
 SENT: THURSDAY, OCTOBER 06, 2016 2:13 PM
 TO: MATT STILL ; FRANK WYNES
 
 SUBJECT: RE: 333 DOWNTOWN
  
 MATT AND FRANK,
  
 HERE IS THE ANSWER. IF THEY ARE REVIEWING THE SMOKE
 CONTROL FANS WITH UL RATING THAT WE HAVE UNDER
 SUBMITTAL RIGHT NOW, HERE IS THE BELT COUNT.
  
 LPF-1 GROOVE DRIVE ? 1 BELT
 SPF-1-1 2 GROOVE DRIVE ? 2 BELTS
 SPF1-2 2 GROOVE DRIVE ? 2 BELTS
 SPF-R-1 1 GROOVE DRIVE -1 BELT
 SPF-R-2 1 GROOVE DRIVE ? 1 BELT
  
  
 LET ME KNOW IF I CAN BE OF MORE ASSISTANCE.
  
 THANKS,
  
 BEST REGARDS,
  
 JIM WALKER
 SALES ENGINEER
  
 ** SEND QUOTE REQUESTS TO [email protected]
 ** CC TO ME [email protected]
  
 TOM BARROW COMPANY - TAMPA
 OFFICE: 813-888-9000 EXT. 223
 MOBILE: 813-401-6755
 WWW.TOMBARROW.COM
 AIR COOLED CHILLERS IN STOCK
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved