Plan Review Notes For Permit 16100008 |
Permit Number |
16100008 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-11-22 15:03:24 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16100008 | | 11/22/16 | | | | 1) THE SUBMITTED SPECS FOR THE PIZZA OVEN AND THE | | GREASE DUCT EACH SPECIFY COMPLIANCE WITH NFPA 96. | | PLEASE REFER TO SECTION 7.8.2.1(8) . A HINGED UPBLAST | | FAN IS REQUIRED FOR THE GREASE DUCT TERMINATING AT THE | | ROOFTOP. | | | | 2) PLEASE CORRECT PLAN KEY NOTE #13 SPECIFYING THE | | WRONG TYPE OF EXHAUST DUCTWORK. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|