2017-07-21 10:22:592ND REVIEW FBC-2014 MECHANICAL
 PERMIT SUBMITTAL #16100003
 7/21/17
  
 1) THE X-VENT BOXES ARE APPROVED.
  
 2) THE SUBMITTED SPECS FOR THE DRYER MODEL #GUD27ESSJWW
 SHOWS A MAXIMUM EXHAUST DUCT LENGTH OF 56 FT. USING A
 4" DUCT AND 4" TERMINATION, HOWEVER THE UNITS PLANS ARE
 SPECIFYING MINIMUMS OF 64 FT. TO 200 FT. DEPENDING ON
 THE UNIT. PLEASE INDICATE BY UNIT NUMBER WHERE THESE
 DRYERS ARE TO BE INSTALLED. PROVIDE UNIT NUMBERS TAT
 CORRELATE TO THE NUMBERS SHOWN ON THE PLANS.
  