Plan Review Notes For Permit 16100003 |
Permit Number |
16100003 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-07-21 10:22:59 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT SUBMITTAL #16100003 | | 7/21/17 | | | | 1) THE X-VENT BOXES ARE APPROVED. | | | | 2) THE SUBMITTED SPECS FOR THE DRYER MODEL #GUD27ESSJWW | | SHOWS A MAXIMUM EXHAUST DUCT LENGTH OF 56 FT. USING A | | 4" DUCT AND 4" TERMINATION, HOWEVER THE UNITS PLANS ARE | | SPECIFYING MINIMUMS OF 64 FT. TO 200 FT. DEPENDING ON | | THE UNIT. PLEASE INDICATE BY UNIT NUMBER WHERE THESE | | DRYERS ARE TO BE INSTALLED. PROVIDE UNIT NUMBERS TAT | | CORRELATE TO THE NUMBERS SHOWN ON THE PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|