Plan Review Notes
Plan Review Notes For Permit 16100003
Permit Number 16100003
Review Stop M
Sequence Number 1
Notes
Date Text
2016-10-04 12:22:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100003
 10/4/16
  
 1) XVENT BOX SUBMITTALS: PLEASE REVIEW SECTION 501.3,2
 PRINTED BELOW AND VERIFY COMPLIANCE.
  
 501.3.2 EXHAUST OPENING PROTECTION.
 EXHAUST OPENINGS THAT TERMINATE OUTDOORS SHALL BE
 PROTECTED WITH CORROSION-RESISTANT SCREENS, LOUVERS OR
 GRILLES. OPENINGS IN SCREENS, LOUVERS AND GRILLES SHALL
 BE SIZED NOT LESS THAN 1/4 INCH (6 MM) AND NOT LARGER
 THAN 1/2 INCH (13 MM). OPENINGS SHALL BE PROTECTED
 AGAINST LOCAL WEATHER CONDITIONS. LOUVERS THAT PROTECT
 EXHAUST OPENINGS IN STRUCTURES LOCATED IN
 HURRICANE-PRONE REGIONS, AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING, SHALL COMPLY WITH AMCA
 STANDARD 550. OUTDOOR OPENINGS LOCATED IN EXTERIOR
 WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR WALL
 OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  