Plan Review Notes For Permit 16091122 |
Permit Number |
16091122 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-14 14:18:38 | JOB PERMIT NUMBER: 16091122 | | JOB ADDRESS: 534 18TH ST | | WEST PALM BEACH FLORIDA | | DATE: NOVEMBER 14, 2016 | | ELECTRICAL PLAN REVIEW COMMENTS | | | | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA | | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH | | AMENDMENTS. BELOW SEE THE UN-ADDRESSED COMMENTS. | | | | 1] ADDRESSED | | | | 2] NOT ADDRESSED, SHOW SERVICE RACEWAY AND CONDUCTOR | | SIZES ON THE RISER DIAGRAM (ORIGINAL COMMENT). PLEASE | | SHOW WIRE SIZE FROM METER TO MAIN, SHOW FEEDER CONDUIT | | TYPE FROM MAIN TO PANEL "A" (PVC,RMC,EMT, & ETC), | | CLARIFY IF ALUMINUM SE/USE CABLE OR INDIVIDUAL 4/0 | | CONDUCTORS ARE IN 1 1/2" CONDUIT AND VERIFY NEC TABLE 9 | | FOR CONDUIT FILL. | | | | 3] ADDRESSED | | | | 4] ADDRESSED | | | | 5] ADDRESSED | | | | 6] ADDRESSED | | | | 7] ADDRESSED | | | | 8] ADDRESSED | | | | 9] ADDRESSED | | | | 10] ADDRESSED | | | | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER | | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES | | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER | | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME | | DIRECTLY. | | | | 2ND REVIEW FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | |
|