| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| AMENDMENTS. BELOW IS A LIST OF ITEMS NOTED. |
| |
| 1] CORRECT COVER SHEET A-1 TO INDICATE THE CURRENT |
| APPLICABLE CODES NEC 2011 & FBC-R 2014. |
| |
| 2] SHOW SERVICE RACEWAY AND CONDUCTOR SIZES ON THE |
| RISER DIAGRAM. (FROM FPL METER TO MAIN DISCONNECT) |
| FBC-107 |
| |
| 3] SHOW THE LOCATION OF SERVICE EQUIPMENT AND SUB-PANEL |
| ON THE ELECT FLOOR PLAN. FBC-107 |
| |
| 4] PROVIDE A LEGEND TO HELP IDENTIFY SOME QUESTIONABLE |
| MARKS. FBC-107 |
| |
| 5] PLEASE DARKEN ELECT FLOOR PLAN TO CLEARLY VIEW ALL |
| POINTS AND LABEL EACH ROOM WITH INTENDED USE. FBC-107 |
| |
| 6] CORRECT PANEL SCHEDULE FOR BATHROOM CIRCUIT #9 |
| REFLECTING A 14 GAUGE WIRE WITH A 20 AMP BREAKER? IF |
| CIRCUIT DESIGNATION IS INTENDED FOR THE BATH GFCI |
| RECEPTACLE OUTLET IT SHALL BE FED WITH A MINIMUM 12 AWG |
| WIRE AND PROTECTED BY A 20 AMP BREAKER. FBC-R SEC |
| E3703.4 |
| |
| 7] ADD A BLOCK NOTE INDICATING GENERAL ELECT |
| REQUIREMENTS FOR ARC-FAULT PROTECTION AND |
| TAMPER-RESISTANT RECEPTACLES. FBC-R SECTIONS E4002.14 & |
| E3902.12 |
| |
| 8] ADD A NOTE FOR SMOKE ALARMS IN ACCORDANCE WITH FBC-R |
| 314 & 315. |
| |
| 9] KITCHEN COUNTER-TOPS, BATHROOM SINK COUNTERS, AND |
| OUTDOOR RECEPTACLES OUTLETS SHALL HAVE GFCI PROTECTION |
| PER FBC-R SECTIONS E3902.1, E3902.3, & E3902.6. SHOW |
| COMPLIANCE. |
| |
| 10] ATTIC ENTRANCE ACCESS REQUIRES A SWITCHED |
| CONTROLLED LIGHTING OUTLET PER FBC-R SEC E3903.4. SHOW |
| COMPLIANCE. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED ITEMS.WHEN RESUBMITTING, FOR A QUICKER RETURN |
| ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES |
| WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |