Plan Review Notes For Permit 16091117 |
Permit Number |
16091117 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-21 18:04:26 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16091117 | | 11/21/16 | | | | 1) COMMENT #8 FROM THE 1ST REVIEW ABOUT THE DIRECTIONAL | | ORIENTATIONS FOR THE ROOMS, WALLS, WINDOW GLASS ETC. IN | | THE MANUAL J STILL EXISTS. PLEASE COMPLY. | | | | 2) COMMENTS #10 A, B, & C FROM THE 1ST REVIEW STILL | | EXIST. PLEASE COMPLY | | | | 3) FORM R405-2014 LISTS THE AC SYSTEM AT 16 SEER BUT | | THE NEW AC SCHEDULE INDICATES A 14 SEER SYSTEM. | | | | 4) PLEASE REMOVE THE FOUNDATION PLAN FROM THE MA-2 PLAN | | SHEET. THE FOUNDATION DRAWING REQUIRES A SIGNATURE AND | | SEAL BY A FL. LICENSED ENGINEER OR ARCHITECT. | | | | 5) A SEALED ENCLOSURE IS REQUIRED FOR THE AIR HANDLER | | RETURN IF IT IS TO BE LOCATED IN THE UTILITY ROOM- SEE | | SECTION R403.2.2 FBC-14 ENERGY CONSERVATION AND SECTION | | M1602.2 (3) FBC-14 RESIDENTIAL. | | | | 6) THE 9" TRANSFER DUCT FROM BEDROOM 1 IS UNDERSIZED. | | THE MINIMUM SIZE MUST BE 10" PER SECTION M1602.4 FBC-14 | | MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|