Plan Review Notes For Permit 16091117
Permit Number 16091117
Review Stop M
Sequence Number 2
Notes
Date Text
2016-11-21 18:04:262ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16091117
 11/21/16
  
 1) COMMENT #8 FROM THE 1ST REVIEW ABOUT THE DIRECTIONAL
 ORIENTATIONS FOR THE ROOMS, WALLS, WINDOW GLASS ETC. IN
 THE MANUAL J STILL EXISTS. PLEASE COMPLY.
  
 2) COMMENTS #10 A, B, & C FROM THE 1ST REVIEW STILL
 EXIST. PLEASE COMPLY
  
 3) FORM R405-2014 LISTS THE AC SYSTEM AT 16 SEER BUT
 THE NEW AC SCHEDULE INDICATES A 14 SEER SYSTEM.
  
 4) PLEASE REMOVE THE FOUNDATION PLAN FROM THE MA-2 PLAN
 SHEET. THE FOUNDATION DRAWING REQUIRES A SIGNATURE AND
 SEAL BY A FL. LICENSED ENGINEER OR ARCHITECT.
  
 5) A SEALED ENCLOSURE IS REQUIRED FOR THE AIR HANDLER
 RETURN IF IT IS TO BE LOCATED IN THE UTILITY ROOM- SEE
 SECTION R403.2.2 FBC-14 ENERGY CONSERVATION AND SECTION
 M1602.2 (3) FBC-14 RESIDENTIAL.
  
 6) THE 9" TRANSFER DUCT FROM BEDROOM 1 IS UNDERSIZED.
 THE MINIMUM SIZE MUST BE 10" PER SECTION M1602.4 FBC-14
 MECHANICAL.
  