2016-11-21 17:41:20 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16091111 | | 11/21/16 | | | | 1) COMMENT #8 FROM THE 1ST REVIEW ABOUT THE DIRECTIONAL | | ORIENTATIONS FOR WALLS, WINDOW GLASS ETC. IN THE MANUAL | | J STILL EXISTS. IN ADDITION, THE BEDROOM LABELING IN | | THE CALCS DOES NOT MATCH THE LABELING ON THE PLAN WHICH | | IS 1, 2, & MASTER BEDROOM-3. | | | | 2) COMMENTS #10 A, B, & C FROM THE 1ST REVIEW STILL | | EXIST. IN ADDTION THE ENERGY COMPLIANCE FORM R405-2014 | | LISTS 2 AS THE NUMBER OF BEDROOMS- 3 BEDROOMS ARE SHOWN | | ON THE PLAN. | | | | 3) FORM R405-2014 LISTS THE AC SYSTEM AT 16 SEER BUT | | THE NEW AC SCHEDULE INDICATES A 14 SEER SYSTEM. | | | | 4) PLEASE REMOVE THE FOUNDATION PLAN AND WINDOW | | SCHEDULE FROM THE MA-2 PLAN SHEET. THOSE DRAWINGS AND | | DETAILS BELONG ON AN ARCHITECTURAL OR STRUCTURAL SHEET, | | AND THE FOUNDATION DRAWING REQUIRES A SIGNATURE AND | | SEAL BY A FL. LICENSED ENGINEER OR ARCHITECT. | | | | 5) A SEALED ENCLOSURE IS REQUIRED FOR THE AIR HANDLER | | RETURN IF IT IS TO BE LOCATED IN THE UTILITY ROOM- SEE | | SECTION R403.2.2 FBC-14 ENERGY CONSERVATION AND SECTION | | M1602.2 (3) FBC-14 RESIDENTIAL. | | | | 6) PLEASE REMOVE THE BLANK A-5 SHEET FROM THE PLAN | | SETS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|