Plan Review Notes
Plan Review Notes For Permit 16091111
Permit Number 16091111
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-08 13:57:391ST REVIEW FBC-2014 RESIDENTIAL, ENERGY CONSERVATION
 PERMIT #16091117
 11/8/16
  
 1) THE AC PLAN ON A-2 AND THE AC SIZING CALCULATIONS
 MUST BEAR THE SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
 PLEASE NOTE THAT ONLY FL. LICENSED DESIGN PROFESSIONALS
 OR INSTALLING AC CONTRACTORS ARE PERMITTED TO DRAW AC
 PLANS PER SECTION 105.3.1.2
  
 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN-
 SECTION R403.6.1 FBC-14 ENERGY CONSERVATION
  
 3) INDICATE THE BRANCH DUCT AND DIFFUSER SIZES- ONLY
 THE MAIN TRUCKS HAVE BEEN SIZED- SECTION 107.3.5.1.4.
  
 4) SHOW THE CONDENSATE PIPING RUN AND DISPOSAL
 LOCATION- SECTION M1411.3 FBC- RESIDENTIAL.
  
 5) SHOW THE DRYER VENT RUN AND TERMINATION LOCATION.
 INDICATE THE TYPE AND SIZE OF VENT AND VENT CAP-
 SECTION M1502.
  
 6) INDICATE THE TYPE OF KITCHEN EXHAUST TO BE INSTALLED
 AND PROVIDE SPECIFICATIONS- REFER TO SECTION M1503-
 M1507 FBC-RESIDENTIAL.
  
 7) PROVIDE A NUMBER FOR EACH BEDROOM- 1,2,3, OR 4 ON
 THE FLOOR PLAN SO THE PLAN MATCHES THE MANUAL J
 WORKSHEETS.
  
 8) THE DIRECTIONAL ORIENTATIONS SHOWN IN THE MANUAL J
 WORKSHEETS FOR WINDOWS AND DOORS DO NOT APPEAR TO MATCH
 THEIR DIRECTIONAL ORIENTATIONS ON THE PLAN.
  
 9) SHOW THE LOCATION OF THE AC CONDENSER AND PROVIDE
 DETAILS FOR INSTALLATION OF THE MOUNTING PAD AND
 ANCHORING THE CONDENSER- SECTIONS M1305.1.4.1, AND
 M1401.4.
  
 10) ENERGY FORM R405-2014:
  
 A) PLEASE FILL IN ALL THE REQUESTED INFORMATION AT THE
 TOP OF PAGE 1- OWNER, BUILDER NAME, PERMIT OFFICE,
 PERMIT NUMBER, JURISDICTION. CORRECT THE CLIMATE ZONE 2
 DESIGNATION TO 1A PER TABLE R301.1.
  
 B) THE SUBMITTED ENERGY FORM IS INDICATING A "WORST
 CASE" COMPLIANCE, HOWEVER A WORST CASE COMPLIANCE IS
 USED FOR MODEL HOMES AND NOT FOR INDIVIDUAL RESIDENCES
 AS NOTED IN SECTION R405.4.2 EXCEPTION, ENERGY
 CONSERVATION. PLEASE CORRECT PAGE 1 AND PAGE 4, AND
 REVISE THE WINDOW ORIENTATIONS SO THEY MATCH WITH THE
 ORIENTATIONS TO BE SHOWN ON THE CORRECTED MANUAL J
 WORKSHEETS.
  
 C) COMPLETE THE AIR BARRIER AND INSULATION INSPECTION
 CHECKLIST AND ALL REQUIRED INFORMATION AT THE TOP OF
 THE PAGE- OWNER, BUILDER NAME, PERMIT OFFICE, PERMIT
 NUMBER, JURISDICTION.
  
 11) PLEASE SUBMIT TWO SETS OF CORRECTED PLANS PER
 SECTION 107.1 WPB AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  