Plan Review Notes
Plan Review Notes For Permit 16091111
Permit Number 16091111
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-18 09:27:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 3. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI
 DEVICE. FBC RES E3902.3
 4. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE
 PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE
 HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET
 THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2
 ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5
 5. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT
 RECEPTACLE THROUGHOUT. FBC RES E4002.14
 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 7. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY DESIGNER
 OF RECORD. FBC 107.3.5
 8. EXTERIOR RECEPTACLES TO BE GFCI PROTECTED, LABEL AT
 THE PANEL CIRCUIT #26 FBC RES E3902.3
 9. ADDRESS SPACING FOR COUNTERTOP RECEPTACLES IN
 KITCHEN PER FBC RES E3901.4 NEXT TO REF. AREA AND
 ISLAND.
 10. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION
 PER FBC RES E3903.4
 11. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC
 RES E3902.12
 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  