2016-10-18 09:27:33 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA RES BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND |
| LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC |
| RATINGS. FBC 107.3.5 |
| 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS |
| FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5 |
| 3. SHOW EXTERIOR RECEPTACLE AT REAR PROTECTED BY GFCI |
| DEVICE. FBC RES E3902.3 |
| 4. PLEASE NOTE THAT ALL CIRCUITS? DESIGNATION AT THE |
| PANELBOARDS MUST INDICATE WHAT AREA SPECIFICALLY OF THE |
| HOUSE IT?S SERVICING. GENERAL LIGHTING DOES NOT MEET |
| THESE REQUIREMENTS. EXAMPLE, LABEL BEDROOM 1, BEDROOM 2 |
| ETC.?NEC 408.4 FIELD ID REQUIRED. FBC 107.3.5 |
| 5. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT |
| RECEPTACLE THROUGHOUT. FBC RES E4002.14 |
| 6. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO |
| INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. |
| 7. ELECTRICAL SHEET TO BE SIGNED AND SEALED BY DESIGNER |
| OF RECORD. FBC 107.3.5 |
| 8. EXTERIOR RECEPTACLES TO BE GFCI PROTECTED, LABEL AT |
| THE PANEL CIRCUIT #26 FBC RES E3902.3 |
| 9. ADDRESS SPACING FOR COUNTERTOP RECEPTACLES IN |
| KITCHEN PER FBC RES E3901.4 NEXT TO REF. AREA AND |
| ISLAND. |
| 10. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION |
| PER FBC RES E3903.4 |
| 11. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC |
| RES E3902.12 |
| 12. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY |
| QUESTIONS OR CONCERNS. |
| |