2016-09-28 09:38:42 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- SIZE OF TRANSFER DUCT SHOWN FOR THE MASTER BEDROOM | | DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS | | REQUIRED. NOTE: NEED TO CONSIDER ALL THE SUPPLY AIR | | INTO THE MASTER BEDROOM, INCLUDING BATHROOM AND | | CLOSETS. SEE EXCEPTION #3 ON SEC. M1602.4 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | 2- SPECIFY SIZE OF TRANSFER DUCT FOR BEDROOM #2. SEC. | | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|