2016-09-28 09:38:42RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SIZE OF TRANSFER DUCT SHOWN FOR THE MASTER BEDROOM
 DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. NOTE: NEED TO CONSIDER ALL THE SUPPLY AIR
 INTO THE MASTER BEDROOM, INCLUDING BATHROOM AND
 CLOSETS. SEE EXCEPTION #3 ON SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- SPECIFY SIZE OF TRANSFER DUCT FOR BEDROOM #2. SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  