Plan Review Notes
Plan Review Notes For Permit 16090930
Permit Number 16090930
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-11 09:20:26PLEASE PROVIDE AN ELECTRICAL LOAD CALCULATION AND A
 ACCURATE RISER DIAGRAM AND PANEL SCHEDULE REFLECTING
 POOL HEATER LOADS (50AMPS) AS SHOWN ON SPECS PROVIDED.
 SHOW EXISTING MAIN AMPERAGE SERVICE SIZE TO VERIFY
 CAPACITY FOR NEW POOL LOADS ADDED. FBC 107.3.5
  
 VAL PEREZ
 *6717
  