2016-11-01 07:09:43PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE EXISTING SINGLE FAMILY STRUCTURE HAS A
 IMPROVEMENT VALUE OF MORE THAN $300,000.00. SECTION
 708.8 OF THE FBC EXISTING BUILDING REQUIRES:
 (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 708.8.1.
 (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15-PERCENT INCREASE IN
 THE COST OF REROOFING.
 SHOW HOW THIS WILL BE ACCOMPLISHED.
 THE BUILDING CODE DOES NOT HAVE A PROVISION THAT ALLOWS
 THE OWNER TO CHOSE NOT TO COMPLY WITH A CODE
 REQUIREMENT.
 2016 FLORIDA STATUTES 553.844 WINDSTORM LOSS
 MITIGATION; REQUIREMENTS FOR ROOFS AND OPENING
 PROTECTION.
 3. PRESCRIPTIVE TECHNIQUES FOR IMPROVEMENT OF
 ROOF-TO-WALL CONNECTIONS. THE LEGISLATURE RECOGNIZES
 THAT THE COST OF RETROFITTING EXISTING BUILDINGS TO
 MEET THE CODE REQUIREMENTS FOR NEW CONSTRUCTION IN THIS
 REGARD MAY EXCEED THE PRACTICAL BENEFIT TO BE ATTAINED.
 THE LEGISLATURE INTENDS FOR THE COMMISSION TO PROVIDE
 FOR THE INTEGRATION OF ALTERNATE, LOWER-COST MEANS THAT
 MAY BE EMPLOYED TO RETROFIT EXISTING BUILDINGS THAT ARE
 NOT OTHERWISE REQUIRED TO COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE FOR NEW CONSTRUCTION SO
 THAT THE COST OF SUCH IMPROVEMENTS DOES NOT EXCEED
 APPROXIMATELY 15 PERCENT OF THE COST OF REROOFING.
 ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED UNLESS
 EVALUATION AND INSTALLATION OF CONNECTIONS AT GABLE
 ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15 PERCENT OF
 THE COST OF ROOF REPLACEMENT. FOR HOUSES THAT HAVE BOTH
 HIP AND GABLE ROOF ENDS, THE PRIORITY SHALL BE TO
 RETROFIT THE GABLE END ROOF-TO-WALL CONNECTIONS UNLESS
 THE WIDTH OF THE HIP IS MORE THAN 1.5 TIMES GREATER
 THAN THE WIDTH OF THE GABLE END. PRIORITY SHALL BE
 GIVEN TO CONNECTING THE CORNERS OF ROOFS TO WALLS BELOW
 THE LOCATIONS AT WHICH THE SPANS OF THE ROOFING MEMBERS
 ARE GREATEST;
 4.?STRENGTHENING OR CORRECTING ROOF-DECKING ATTACHMENTS
 AND FASTENERS DURING REROOFING; AND
 5.?ADDING OR STRENGTHENING OPENING PROTECTIONS.
  
  