2016-09-27 17:12:53 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE CONTRACT THAT WAS SUBMITTED INDICATES THAT A NEW | | 2' X 4' SKYLIGHT IS TO BE INSTALLED. PLEASE CLARIFY IF | | AN EXISTING SKYLIGHT IS TO BE REPLACED OR A NEW ONE IS | | TO BE INSTALLED WHICH WOULD REQUIRED STRUCTURAL FRAMING | | OF THE OPENING THROUGH THE ROOF AND CEILING, WALL | | COVERING, INSULATION, ETC. FBC107.2.1 | | | | 2) PROVIDE A ROOF PLAN THAT SHOWS THE EXACT LOCATION OF | | THE SKYLIGHT AND WHAT ROOF ZONE IT IS IN. FBC 301.2.1 | | AND FIGURE R301.2(7) | | | | 3) NONE OF THE PRODUCT APPROVALS THAT WERE SUBMITTED | | FOR THE ROOF TILES OR THE ROOF TILE ADHESIVES LISTS THE | | ATTACHMENT RESISTANCE VALUES. THE ROOF TILE ASSEMBLY'S | | ATTACHMENT RESISTANCE IS REQUIRED TO DETERMINE | | COMPLIANCE WITH FBC R905.3. | | | | |
|