2016-10-22 09:14:06 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16090860 |
| ADD: 1301 SUMMIT BLVD/ LORIKEET BIRD EXHIBIT |
| CONT: GAST |
| TEL: 561-281-1001 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: SAT. OCT 22/2016 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE THIS PROJECT IS LOCATED IN A |
| QUESTIONABLE SOILS AREA, PLEASE PROVIDE SIGNED & SEALED |
| ORIGINAL SOILS REPORTS MINIMUM OF 2 REPORTS. 2014 FBC-B |
| W/ 2016 SUPPLEMENTS, 1803.5.2 QUESTIONABLE SOIL. |
| |
| 2) THIS PROPERTY IS ALSO LOCATED IN A FLOOD ZONE. FBC |
| BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A 7" FLOOD |
| ZONE, BFE ELEVATION 12 FEET NGVD. A FLOOD ELEVATION |
| CERTIFICATE WILL BE REQUIRED. THE CITY OF WEST PALM |
| BEACH IS STILL USING THE 1929 NGVD ELEVATION DATUM. NO |
| FIS FOR THIS LOCATION. |
| IMPORTANT CHANGE!!!! |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL (1FOOT) FREEBOARD OF ELEVATION. |
| CITY ORDINANCE CHANGE SEPT. 12/2016. PLEASE ALSO NOTE |
| FOR FUTURE WORK IN THE CITY?S FLOOD ZONE AREAS, THE |
| CITY COMMISSION & MAYOR WILL BE CHANGING THE FREEBOARD |
| REQUIREMENTS TO (2 FOOT) FREEBOARD IN THE UPCOMING |
| MONTHS. ALSO ON ALL FLOOD ZONE CERTIFICATES THE |
| LATITUDE AND LONGITUDE ARE TO BE FILLED OUT WITH THE |
| FRONT CENTER OF THE STRUCTURE BEING THE POINT GIVEN. |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (2.1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF |
| THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH |
| FLOOR HEIGHT. 107.2.5.1 DESIGN FLOOD ELEVATIONS. |
| 107.3.5.1.1(1) MINIMUM PLAN REVIEW COMMERCIAL |
| BUILDINGS. FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN |
| FLOOD ELEVATIONS. |
| |
| (2.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED. REQUIRED |
| INSPECTIONS. 110.3.( 1.2.) IN FLOOD HAZARD AREAS, UPON |
| PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, |
| AND PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE |
| ELEVATION CERTIFICATION, REQUIRED IN SECTION 1612.5, |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL. |
| |
| (2.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANTS. REQUIRED INSPECTIONS. 110.3.( 6.) FINAL |
| INSPECTION. TO BE MADE AFTER THE BUILDING IS COMPLETED |
| AND READY FOR OCCUPANCY.6.1. LOWEST FLOOR ELEVATION. IN |
| FLOOD HAZARD AREAS, AS PART OF THE FINAL INSPECTION, A |
| FINAL CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL |
| BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION. |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| OMB NO. 1660-0008 |
| EXPIRATION DATE: NOV. 30/2018 |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| 3A) SHEET A-101 ON THE RIGHT SIDE OF THIS SHEET THE |
| PLANS HAVE AN EGRESS LEGEND FOR MAIN EGRESS PLAN AND |
| THE SECONDARY EGRESS PLAN. PLEASE NOTE THE PLANS DO NOT |
| INDICATE ANY MAIN OR SECONDARY EGRESS REQUIREMENTS. |
| FBC-B TABLE 1014.3 FOR AN ASSEMBLY OCCUPANCY COMMON |
| PATH OF TRAVEL IS 75 FEET WITHOUT FIRE SPRINKLERS. NOTE |
| IF 2 EGRESSES ARE REQUIRED BECAUSE THE COMMON PATH OF |
| TRAVEL IS EXCEEDED THEN THEY MUST BE ? THE DIAGONAL |
| DISTANCE APART. SEE 1015.2.1. FBC-B 2014 W/2016 |
| UPDATES. |
| |
| 3B) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10 |
| ALL SHOW SPACED PURLINS AND NOT SOLID PLYWOOD |
| SHEATHING. FBC-B REQUIRES STRUCTURAL ROOF SHEATHING. |
| |
| 3C) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10 DO |
| NOT INDICATE THE TYPE OF METAL ROOF SYSTEM IS TO BE |
| APPLIED. SHEET A-200 NOTE #1 INDICATES THE ROOF SYSTEM |
| IS TO BE A METAL CORRUGATED GALVANIZED METAL ROOF |
| SYSTEM, NO MENTION OF GAUGE, PRODUCT APPROVAL IF THIS |
| SYSTEM IS ARCHITECTURAL REQUIRING SOLID ROOF SHEATHING |
| BENEATH OR IF THIS ROOFING SYSTEM IS A STRUCTURAL ROOF |
| PANEL SYSTEM. NOTE IF THE SYSTEM IS TO BE A STRUCTURAL |
| ROOF PANEL SYSTEM AND IS TO BE ATTACHED TO WOOD FRAMING |
| MEMBERS THE VALUES FOR THE FASTENERS IN THE PRODUCT |
| APPROVAL WILL ALSO NEED REFLECT TESTING IN THE SAME |
| TYPE OF SPECIES OF LUMBER AND GRADE. 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3D) SHEET A-101 DETAIL # 4 & SHEET S4.0 DETAILS 6-10, |
| THERE IS A DISCREPANCY IN PLANS, THE SHEET A-101 DETAIL |
| # 4 SHOWS 2 X4 PURLINS WITHIN THE BUILDING, SPACING |
| UNKNOWN WHEREAS THE S-4.0 SHEET DETAILS 6-10 ALL SHOW 2 |
| INCH DIAMETER PURLINS, SPACING UNKNOWN. PLEASE SHOW |
| COMPLIANCE WITH 2308.10.5 PURLINS OF THE FBC-B THE |
| MAXIMUM SPAN OF 2-INCH BY 4-INCH (51 MM BY 102 MM) |
| PURLINS SHALL BE 4 FEET (1219 MM). THE MAXIMUM SPAN OF |
| THE 2-INCH BY 6-INCH (51 MM BY 152 MM) PURLIN SHALL BE |
| 6 FEET (1829 MM), BUT IN NO CASE SHALL THE PURLIN BE |
| SMALLER THAN THE SUPPORTED RAFTER. |
| |
| 3E) SHEET S4 DETAIL # 7 IS SHOWING A GABLE PORTION OF |
| ROOF FRAMING AND SHED TYPE FRAMING THAT ATTACH TO A 8 |
| INCH HORIZONTAL WOOD BEAM. PLEASE SEE THE SHED ROOF |
| FRAMING 4 INCH DIAMETER FRAMING MEMBERS ARE ATTACHED TO |
| THE 8 INCH WOOD BEAM WITH ? X 8 INCH LAG SCREWS, |
| WHEREAS THE GABLE END ROOF FRAMING IS CUT TO SIT ON TOP |
| OF THE SHED ROOF FRAMING MEMBERS TAPERED TO NOTHING AND |
| SCREWED INTO THE SHED ROOF FRAMING MEMBERS WITH 4 INCH |
| WOOD SCREWS, THE DIAMETER UNKNOWN? THE GABLE ROOF |
| FRAMING MEMBER SHOULD TIE IN DIRECTLY TO THE 8 INCH |
| WOOD BEAM( EQUIVALENT TO THE DOUBLE TOP PLATE) NOT A |
| TAPERED CUT WITH LESS VALUE IN THE FRAMING. SEE 2014 |
| FBC-B 2308.10.1. |
| |
| 3F) PLEASE PROVIDE THE VALUE OF THE 8 INCH LAG SCREW |
| FOR WITHDRAW (UPLIFT) VALUES FOR THE TYPE OF WOOD |
| PURPOSED. PLEASE PROVIDE THE REQUIRED VALUES TO RESIST |
| UPLIFT FOR EACH OF THE FRAMING MEMBERS SINCE THESE ARE |
| NOT TRUSSES BUT ROOF RAFTERS/ JOIST THAT APPEAR WILL BE |
| CUT ON THE JOB. SHOW COMPLIANCE WITH |
| FBC-B 2308.10.1 WIND UPLIFT. THE ROOF CONSTRUCTION |
| SHALL HAVE RAFTER AND TRUSS TIES TO THE WALL BELOW. |
| RESULTANT UPLIFT LOADS SHALL BE TRANSFERRED TO THE |
| FOUNDATION USING A CONTINUOUS LOAD PATH. THE RAFTER OR |
| TRUSS TO WALL CONNECTION SHALL COMPLY WITH TABLES |
| 2304.9.1 AND 2308.10. |
| |
| 3G) SHEET S4 DETAILS 9 & 10 ARE MISSING A RIDGE BOARD |
| INCOMPLIANCE WITH FBC-B 2308.10.4. 2308.10.4 CEILING |
| JOIST AND RAFTER FRAMING. RAFTERS SHALL BE FRAMED |
| DIRECTLY OPPOSITE EACH OTHER AT THE RIDGE. THERE SHALL |
| BE A RIDGE BOARD AT LEAST 1-INCH (25 MM) NOMINAL |
| THICKNESS AT RIDGES AND NOT LESS IN DEPTH THAN THE CUT |
| END OF THE RAFTER. AT VALLEYS AND HIPS, THERE SHALL BE |
| A SINGLE VALLEY OR HIP RAFTER NOT LESS THAN 2-INCH (51 |
| MM) NOMINAL THICKNESS AND NOT LESS IN DEPTH THAN THE |
| CUT END OF THE RAFTER. |
| |
| 4A) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (C) PANEL WALLS:, WALL LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |