Plan Review Notes For Permit 16090794 |
Permit Number |
16090794 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-24 02:24:30 | 1) SUBMIT SIZING CALCULATIONS FOR THE SIZING OF THIS | | GREASE TRAP. 2014 FPC SEC.1003.2, 1003.3.4. | | 2) THESE DEVICES ARE USUALLY EQUIPPED WITH FLOW CONTROL | | DEVICES THAT ARE VENTED. THIS IS NOT SHOWN ON THE | | PLANS. SUBMIT THE INSTALLATION DETAILS FROM THE | | INSTALLATION MANUAL FOR THIS DEVICE.WPB AMEND. TO FBC | | SEC.107.2.1, 1003.3.4.2. | | 3) PLANS DONE IN PENCIL CANNOT BE ACCEPTED AS CHANGES | | CAN BE MADE AFTER APPROVAL OF THE PLANS. | | 4) PLEASE CLARIFY THE TYPE OF FIXTURE DISCHARGING INTO | | THE GREASE INTERCEPTOR. IT APPEARS TO BE A 3 | | COMPARTMENT SINK. IS IT NEW OR EXISTING? IF NEW, SUBMIT | | A WATER RISER ALSO. WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | 5) INDICATE ON THE PLANS IF THIS INTERCEPTOR IS | | REPLACING AN EXISTING UNIT OR IS IT A NEW | | INSTALLATION.IF THE INTERCEPTOR AND SINK ARE NEW SUBMIT | | A FLOOR PLAN SHOWING THE LOCATION OF THE SINK & | | INTERCEPTOR. WPB AMEND. TO FBC SEC.107.2.1, | | 6) IF THE SINK IS NEW, INDICATE ON THE PLAN WHERE THE | | THE 2 INCH DRAIN IS CONNECTING TO THE EXISTING SANITARY | | SYSTEM. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|