Plan Review Notes
Plan Review Notes For Permit 16090660
Permit Number 16090660
Review Stop G
Sequence Number 2
Notes
Date Text
2017-04-26 13:45:191) SUBMIT TWO COPIES OF ALL DOCUMENTS BEING SUBMITTED
 FOR A PERMIT INCLUDING ANOTHER SIGNED & SEALED DRAWING
 FOR THE ANCHORING OF THE LP TANK. WPB AMEND. TO FBC
 SEC.107.1.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 3) SHOW THE LENGTHS OF ALL CUT SECTIONS OF PIPE PER
 2014 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014
 FBC-RES SEC. G2413.
 4) SHOW THE TYPE OF MATERIAL AND PIPE SIZES TO THE
 EXISTING DRYER AND COOKTOP. 2014 FGC SECS. 401.3 &
 401.4. THE EXISTING SYSTEM BTU LOAD MUST BE ADDED TO
 THE NEW BTU LOAD TO ENSURE THE ENTIRE EXISTING SYSTEM
 IS SIZED PROPERLY FOR THE TOTAL BTU LOAD.
 5) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
  
  