Plan Review Notes
Plan Review Notes For Permit 16090660
Permit Number 16090660
Review Stop G
Sequence Number 1
Notes
Date Text
2016-09-21 06:49:591) A SEPARATE PERMIT IS REQUIRED FROM A PLUMBING
 CONTRACTOR FOR THE INSTALLATION OF THE WATER LINES TO
 THE TANKLESS WATER HEATER. F.S. 489.105.
 2) THE WIND LOAD ENGINEERING FOR THE ANCHORING OF THE
 LP TANK IS OUTDATED. THE DOCUMENTS REFER TO THE 2010
 FBC. THE CODE IN EFFECT IS THE 2014 FBC.
 3) THE WIND LOAD ENGINEERING SHALL BE SIGNED AND SEALED
 BY THE DESIGN PROFESSIONAL OF RECORD PER THE FL. ADMIN.
 CODE RULE 61G15-23.002. COPIES HAVE BEEN SUBMITTED. TWO
 COPIES ARE REQUIRED.
 4) THE SUBMITTED WIND LOAD ENGINEERING IS FOR A JOB IN
 VERO BEACH. SUBMIT SIGNED AND SEALED ENGINEERING FOR
 THE ADDRESS WHERE THE WORK IS TO BE DONE.
 5) THE TANKLESS WATER HEATER SHALL BE LISTED AND
 LABELED PER THE 2014 FL. GAS CODE. SEC.301.3, NFPA 58
 SEC. 5.20.1.
 6) INDICATE ON THE SURVEY THE DISTANCE OF THE TANKLESS
 WATER HEATER IN RELATION TO OPERABLE DOORS AND WINDOWS
 OF THE STRUCTURE. THE LOCATION OF THE TANKLESS WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. 2014 FGC SEC. 303.1.
 7) INDICATE ON THE GAS PLAN THAT THE PE PIPE FROM THE
 SECOND STAGE REGULATOR TO THE TANKLESS WATER HEATER IS
 UNDERGROUND.
 8) INDICATE THE TYPE OF PIPE AND SIZE OF THE
 ABOVEGROUND GAS PIPE TO THE WATER HEATER.
 9) PORTIONS OF THE SUBMITTED SHEET FOR THE REGULATORS
 ARE ILLEGIBLE. SUBMIT LEGIBLE COPIES. WPB AMEND. TO FBC
 SEC. 107.2.1.
 10) REMOVE THE PREVIOUS PERRMIT NUMBER THAT IS STAMPED
 ON THE SURVEY. THIS PERMIT NUMBER IS NOT APPLICABLE TO
 THIS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy