Plan Review Notes
Plan Review Notes For Permit 16090638
Permit Number 16090638
Review Stop NFIP
Sequence Number 2
Notes
Date Text
2016-12-09 10:55:29****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ABBREVIATIONS USED (SEE ALSO FBC 1612):
  
 BFE, BASE FLOOD ELEVATION
 DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND
 OTHER REQUIREMENTS)
 FFE, FINISHED FLOOR ELEVATION
 FIRM, FLOOD INSURANCE RATE MAP
 SFHA, SPECIAL FLOOD HAZARD AREA
  
 THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET
 NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY
 APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT.
  
 PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE,
 $480,558
 VALUE OF IMPROVEMENT, $1,000,000
  
 BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23,
 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20,
 WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE
 14 FT NGVD29.
  
 PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH
 ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE TO BE
 AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD LOADS,
 FBC 1612.
  
 7. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS
 TO BE SUBMITTED:
  
 A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND
 IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29).
 B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE
 C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT
 LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO
 THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING.
  
 NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM
 PHOTOGRAPH REQUIREMENTS.
  
 THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO
 DOCUMENT COMPLIANCE WITH FBC 1612.
  
  
  