2016-11-28 12:14:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090638
 11/28/16
  
 1) SYSTEM COMMISSIONING IS REQUIRED IN ACCORDANCE WITH
 SECTION C408 FBC-14 ENERGY CONSERVATION. SEE SECTION
 C408.2.1 AND PROVIDE A COMMISSIONING PLAN.
  
 2) M1.0: CU-1 & 2 ARE LOCATED WITHIN 10' OF THE ROOF
 EDGE. PLEASE VERIFY THAT THERE IS AN EXISTING 42" HIGH
 PARAPET WALL THERE OR PROVIDE A GUARD- SECTION 304.11.
  
 3) CLARIFY HOW ACCESS TO THE ROOFTOP MECHANICAL
 EQUIPMENT IS BEING PROVIDED. IS THERE AN EXISTING ROOF
 LADDER AND HATCH?- SECTION 306.5.
  
 4) OUTDOOR AIR INTAKES SHALL BE LOCATED A MINIMUM OF
 10' FROM STREETS, ALLEYS, PARKING LOTS OR OTHER DRIVE
 AREAS PER SECTION 401.4. PLEASE INDICATE COMPLIANCE ON
 THE PLAN.
  
 5) PLEASE NOTE THAT AN INCREASE IN OCCUPANT LOADS BASED
 ON BUILDING REVIEW COMMENTS MAY RESULT IN INCREASED
 OUTDOOR AIR SUPPLY WHICH WILL REQUIRE REVISED O/A
 CALCULATIONS AND POSSIBLY INCREASED COOLING AND HEATING
 CAPACITIES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER