2016-10-26 08:49:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| ABBREVIATIONS USED (SEE ALSO FBC 1612): |
| |
| BFE, BASE FLOOD ELEVATION |
| DFE, DESIGN FLOOD ELEVATION (BFE PLUS FREEBOARD AND |
| OTHER REQUIREMENTS) |
| FFE, FINISHED FLOOR ELEVATION |
| FIRM, FLOOD INSURANCE RATE MAP |
| SFHA, SPECIAL FLOOD HAZARD AREA |
| |
| THIS STRUCTURE IS LOCATED IN SFHA ZONE A8, BFE 13 FEET |
| NGVD29 PER FIRM. BASED ON PROJECT VALUE AND PROPERTY |
| APPRAISER VALUE OF THE STRUCTURE, THIS IS CONSIDERED A |
| SUBSTANTIAL IMPROVEMENT. |
| |
| PROPERTY APPRAISER PROPOSED 2016 VALUE FOR STRUCTURE, |
| $480,558 |
| VALUE OF IMPROVEMENT, $1,000,000 |
| |
| BASED ON THE SURVEY PROVIDED (MILLER SURVEYING DEC 23, |
| 2015) THE FINISHED FLOOR FOR THIS BUILDING IS 18.20, |
| WHICH COMPLIES WITH THE MINIMUM DFE WHICH APPEARS TO BE |
| 14 FT NGVD29. |
| |
| AS A SUBSTANTIAL IMPROVEMENT, THE FOLLOWING IS |
| REQUIRED: |
| |
| 1. REVISE PLAN TO SHOW ALL EQUIPMENT SERVICING THE |
| BUILDING, EXISTING AND PROPOSED. MECHANICAL EQUIPMENT |
| IS SHOWN ON OTHER PAGES (SUCH AS E4.0). INCORPORATE |
| INTO PLAN WITH PROPOSED ELEVATION. |
| |
| 2. REVISE PLAN TO INCORPORATE THE FFE. |
| |
| 3. REVISE PLAN TO SHOW PROPOSED ELEVATION OF THE BOTTOM |
| OF THE RAMP AND STAIRS. |
| |
| 4. THE SURVEY AND CIVIL PAGES ARE REQUIRED TO BE |
| SIGNED, SEALED DATED ORIGINALS FS471. THESE SHEETS ARE |
| REQUIRED TO SHOW COMPLIANCE WITH FBC 1612 (AND OTHER |
| CODE REQUIREMENTS). |
| |
| 5. PROVISO, PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY |
| WITH ELEVATIONS WILL BE REQUIRED. ALL IMPROVEMENTS ARE |
| TO BE AT OR ABOVE DFE OR BE DESIGNED TO RESIST FLOOD |
| LOADS, FBC 1612. |
| |
| 6. PROVISO, PRIOR TO FINAL INSPECTION, THE FOLLOWING IS |
| TO BE SUBMITTED: |
| |
| A. COMPLETED ELEVATION CERTIFICATE. ALL EQUIPMENT AND |
| IMPROVEMENTS TO BE ABOVE DFE (14 FEET NGVD29). |
| B. PHOTOGRAPHS OF ALL SIDES OF THE STRUCTURE |
| C. PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY EQUIPMENT |
| LOCATED OUTSIDE THE BUILDING SHOWING ITS RELATION TO |
| THE BUILDING AND GROUND AND ITS REQUIRED ANCHORING. |
| |
| NOTE THAT ROOFTOP EQUIPMENT IS NOT EXEMPTED FROM |
| PHOTOGRAPH REQUIREMENTS. |
| |
| THESE REQUIREMENTS ARE FROM CRS ACTIVITY RA3 TO |
| DOCUMENT COMPLIANCE WITH FBC 1612. |
| |
| PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. |
| |
| |