2016-09-28 09:02:16 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #16090638 |
| 9/28/16 |
| |
| 1) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR KITCHEN |
| EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND WALK-IN |
| COOLERS AND FREEZERS. PLEASE PLACE A NOTE ON THE PLAN |
| IN BOLD LETTERS. |
| |
| 2) PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE PLAN |
| PER TABLE 403.3. PROVIDE A SCHEDULE OR TABLE THAT SHOWS |
| THE REQUIRED AND PROVIDED CFMS OF O/A. |
| |
| 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| GAS-FIRED COOKING APPLIANCE- SECTION 304 FBC-14 FUEL |
| GAS. |
| |
| 4) PROVIDE INSTALLATION DETAILS FOR THE AHU'S. |
| |
| 5) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| DETAILS FOR THE AHU'S- SECTION 307. SHOW THE PRIMARY |
| PIPING RUNS AND DISCHARGE LOCATIONS. |
| |
| 6) THE PLAN DESIGNATES ONE TENANT ROOM AS A BAKERY, |
| HOWEVER NO BAKING OVENS ARE SHOWN IN THE SCHEDULES- |
| PLEASE REVIEW AND VERIFY NO BAKING TO BE DONE IN THE |
| ROOM. |
| |
| 7) SHEET M2.0: TRANSFERRED AIR FROM THE FOOD PREP 104 |
| TO THE HALL 100 IS PROHIBITED PER SECTION 601.2. THE |
| LOCATION OF THE GRILL IN THE ROOM IS ALSO NOT IN |
| COMPLIANCE WITH SECTION 918.6. |
| |
| 8) M3.0: TRANSFERRED AIR FROM THE STORAGE 119 TO THE |
| CORRIDOR 120 IS PROHIBITED- SECTION 601.2. |
| |
| 9) SOME OF THE RETURN GRILLS FOR THE AHU'S APPEAR |
| UNDERSIZED FOR THE AMOUNT OF CFMS BEING RETURNED. |
| PLEASE INDICATE WHAT CALULATION METHODOLOGY IS BEING |
| USED FOR SIZING THE GRILLS. |
| |
| 10) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED |
| CLEARANCE DISTANCE MEASUREMENTS FROM AIR INTAKES TO |
| EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF EDGES. |
| |
| 11) SUBMIT THE NOA'S LISTED ON THE PLANS FOR THE ROOF |
| STANDS AND LOUVERS WITH SHOP DRAWING APPROVAL |
| SIGNATURES. PLEASE HIGHLIGHT, CIRCLE, OR OTHERWISE MARK |
| ALL APPLICABLE INSTALLATION DETAILS, NOTES, DESIGN |
| PRESSURES, ETC. ON THE ROOF STAND NOA. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |