2016-10-26 08:59:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC 5TH EDITION, BUILDING |
| |
| 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY IN ADDITION |
| TO A LEVEL II ALTERATION. SHEET ALS1.1, REVISE |
| CLASSIFICATION OF WORK AND REVISE PLAN TO SHOW |
| COMPLIANCE WITH FBC 5TH EDITION EXISTING BUILDING |
| CHAPTER 10 (ALL SECTIONS). |
| |
| 2. FBC EXISTING BUILDING 505, THIS APPEARS TO BE A |
| LEVEL THREE ALTERATION AS THE ENTIRE SPACE IS BEING |
| RECONFIGURED, REVISE PLAN. |
| |
| 3. SEE FBC CHAPTER 2, DEFINITION OF COVERED MALL. IT |
| APPEARS THAT THIS BUILDING MAY FALL UNDER THIS |
| CLASSIFICATION. SEE ALSO FBC 402.1 EXCEPTION 2. REVISE |
| PLAN ACCORDINGLY, OR CONTACT ME TO DISCUSS. |
| |
| 4. SEE NFIP REVIEW. THIS PERMIT WILL BE ISSUED WITH |
| PROVISOS FOR THE DOCUMENTS REQUIRED PRIOR TO CONCRETE |
| POUR AND PRIOR TO FINAL INSPECTION. |
| |
| 5. SEE IMPACT FEE REVIEW. IMPACT FEE ASSESSMENT BY PALM |
| BEACH COUNTY IS REQUIRED PRIOR TO PERMIT ISSUANCE. |
| PLEASE CONTACT THEM DIRECTLY TO COORDINATE. |
| |
| 6. SHEET M5.0, A1.1.1 SHOW THE SECOND FLOOR AS STORAGE. |
| ALS1.1 PROPOSES MERCANTILE FOR THE SECOND FLOOR. FBC |
| 107, CHAPTER 3, PROVIDE PROPOSED OCCUPANCY |
| CLASSIFICATION, TO BE THE SAME ON ALL SHEETS. |
| |
| IF THIS IS DESIGNATED AS STORAGE, PROVIDE INFORMATION |
| REGARDING THE USE OF THE STORAGE AREA. THE PERMIT WILL |
| BE ISSUED WITH PROVISO THAT THIS AREA CANNOT BE USED |
| FOR BUSINESS OR MERCANTILE WITHOUT A PERMIT TO APPLY |
| FOR A CHANGE OF OCCUPANCY. |
| |
| IF THIS IS MERCANTILE, COMPLIANCE WITH ACCESSIBLE ROUTE |
| SHOULD BE SHOWN ON THE PLAN. |
| |
| 7. ALS1.1, PLAN STATES THAT THIS IS BUILDING TYPE VB |
| AND IIB. BUILDING AREA HAS NOT BEEN REVIEWED AS IT IS |
| NOT CLEAR WHICH ONE APPLIES TO THIS PROJECT, FBC 503.1, |
| FBC EXISTING BUILDING 1012.5. |
| |
| 8. ALS1.1, LIFE SAFETY PLAN, COMPLIANCE WITH THE |
| REQUIREMENTS OF FBC CHAPTER 10 NOT CLEAR. |
| |
| FOR INSTANCE, LIFE SAFETY REQUIREMENTS PROVIDES AN |
| OVERALL SQUARE FOOT AREA WITH ONE OCCUPANT LOAD FOR THE |
| MERCANTILE AREA, BUT ALL OF THE MERCANTILE OCCUPANTS |
| ARE DISTRIBUTED THROUGHOUT DIFFERENT AREAS AND DO NOT |
| USE THE SAME EXITS AS THEY ARE IN DIFFERENT PORTIONS OF |
| THE BUILDING. |
| |
| FOR INSTANCE, THREE DIFFERENT AREAS UTILIZE ONE MEANS |
| OF EGRESS COMPONENT (RAMP) BUT IT IS NOT CLEAR HOW MANY |
| OCCUPANTS WILL USE THIS COMPONENT. |
| |
| REVISE PLAN TO INCLUDE THE FOLLOWING: |
| |
| SQUARE FOOT AREA OF EACH SPACE |
| MEANS OF EGRESS WIDTH FOR EACH COMPONENT |
| |
| 9. PROVIDE AN OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, |
| SQUARE FOOT AREA FOR THE FRONT PATIO, ENTRY DECK, REAR |
| PATIO, FBC 1004. |
| |
| 10. FBC 303.4, A3 OCCUPANCY INCLUDES GYMNASIUMS, PLAN |
| PROPOSES BUSINESS FOR THE SPIN AREAS. EXPLAIN RATIONALE |
| OR REVISE PLAN. IF PLAN IS NOT REVISED TO A3, PLEASE |
| EMAIL RATIONALE PRIOR TO RESUBMITTING. |
| |
| 11. PROVIDE INFORMATION REGARDING THE USE OF THE FRONT |
| PATIO AREA FOR SEATING, VENDING, AND EXIT DISCHARGE. IT |
| IS NOT CLEAR HOW MANY OCCUPANTS WILL BE SEATED IN THIS |
| AREA, HOW MANY OCCUPANTS WILL BE FORCED TO TRAVEL |
| THROUGH THIS AREA AS A REQUIRED EXIT DISCHARGE. HOW |
| WILL THE REQUIRED EXIT PATH BE KEPT CLEAR? NO SEATING |
| PLAN WAS SHOWN, BUT MY UNDERSTANDING IS THAT THIS AREA |
| WILL BE USED FOR DINING AND EVENTS. FBC 107. |
| |
| 12. AN OCCUPANT LOAD OF 30 SF PER PERSON FOR MERCANTILE |
| DOES NOT APPEAR TO BE A REASONABLE OCCUPANT LOAD |
| |
| 13. FBC 303.1.2, IT APPEARS THAT THE FOOD AND DRINK |
| VENDORS SHOULD BE CLASSIFIED AS BUSINESS OCCUPANCY OR |
| A2 RATHER THAN MERCANTILE. REVISE OR PROVIDE |
| CLARIFICATION. |
| |
| 14. CLARIFY DESIGN INTENT REGARDING HARDWARE FOR EXIT |
| DOORS A1.1.1. HARDWARE SET 1 IS SPECIFIED FOR THE EXIT |
| DOORS AND INCLUDE A PUSH BAR. IS THE "PUSH BAR" A PANIC |
| DEVICE OR FIRE EXIT HARDWARE IN COMPLIANCE WITH |
| FBC1008.1.10? |
| |
| IT APPEARS THAT THE FOOD AND DRINK VENDING AREAS WITH |
| THEIR SHARED SEATING AREA (REAR PATIO) WILL HAVE AN |
| OCCUPANT LOAD WHICH EXCEEDS 50, SO PANIC BARS WOULD BE |
| REQUIRED, FBC 1008.1.10. IT APPEARS THAT THIS IS |
| DESIGNER?S INTENT. REVISE PLAN TO SPECIFY PANIC BARS |
| FOR HARDWARE SET 1 OR CONTACT ME TO DISCUSS. |
| |
| NOTE THAT 30 SF PER PERSON FOR MERCANTILE IS FOR USES |
| OF MERCANTILE TYPE SPACES; STORES WITH DISPLAYS AND ONE |
| OR TWO CHECK OUT AREAS. THE SPACE PROPOSED INCLUDES |
| ONLY THE CONCENTRATED CHECK OUT AREA TYPE OF SPACE, SO |
| 30 SF PER PERSON DOES NOT APPEAR TO BE A NUMBER |
| CONSISTENT WITH THE USE. |
| |
| NOTE ALSO THAT, WITH PANIC DEVICES, SPACE COMPLIES WITH |
| A2 OCCUPANCY FOR FBC BUILDING. |
| |
| 15. FBC 107, MINIMUM 1/8 INCH SCALE REQUIRED, ALS1.1, |
| A1.1.1. |
| |
| 16. SHOW THE EXIT DISCHARGE FROM THE REAR STAIRS TO THE |
| PUBLIC WAY, FBC 1027. |
| |
| 17. E6 DOES NOT SHOW AN EXIT SIGN AT THE REAR EXIT, FBC |
| 1011.1. |
| |
| 18. ALS1.1, BUILDING DIAGONAL TO SHOW THAT TWO REQUIRED |
| EXITS ARE REMOTELY LOCATED SHOULD MEASURE SPACE WHICH |
| IS SERVED BY THE TWO EXITS. THE DIAGONAL INCLUDES A |
| LARGE SPACE WHICH HAS A SEPARATE EXIT. THE DIMENSION |
| BETWEEN THE TWO EXITS SHOULD MEASURE THE TWO EXITS |
| WHICH SERVE THE SPACE REQUIRING TWO EXITS, FBC |
| 1015.2.1. THE DIMENSION SHOWN MEASURES TWO EXITS |
| SERVING TWO DIFFERENT PORTIONS OF THE BUILDING. |
| |
| 19. REVISE PLAN TO SHOW COMPLIANCE WITH FBC 1006, MEANS |
| OF EGRESS ILLUMINATION, REAR EXIT AND, IF APPLICABLE, |
| THE SECOND EXIT FOR ROOM 134. E6.0, PHM1, DO NOT SHOW |
| ANY LIGHTING FOR THE REAR EXIT AND EXIT DISCHARGE TO |
| THE PUBLIC WAY. |
| |
| 20. REQUIRED FIRE RATED WALLS ARE NOT SHOWN. AT LEAST |
| TWO SIDES OF THE BUILDING LIKELY HAVE FIRE RATING |
| REQUIREMENTS AS THEY SIT IN CLOSE PROXIMITY TO THE |
| PROPERTY LINE. REVISE PLAN TO SHOW ALL FIRE RATED |
| WALLS, FBC TABLE 705.8, FBC EXISTING BUILDING 1012.6. |
| |
| 21. FBC ACCESSIBILITY 207.1, REVISE PLAN TO INDICATE |
| WHICH METHOD OF COMPLIANCE IS ELECTED. |
| |
| 22. THE APPLICATION SUBMITTED IS FOR 1401 CLARE AVENUE, |
| BUT THE PARCEL ID AND SITE ARE CONSISTENT WITH 1301 |
| CLARE AVENUE PER PROPERTY APPRAISER. REVISE PLAN AND |
| APPLICATION OR CLARIFY. IF APPLICANT WOULD LIKE THE |
| ADDRESS CHANGED TO 1401 CLARE AVENUE, PLEASE ADVISE. AT |
| THIS TIME IT APPEARS THAT THE LEGAL ADDRESS FOR THIS |
| PARCEL IS 1301 CLARE AVENUE. |
| |
| 23. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL, FBC 107. THE PRODUCT |
| APPROVALS SUBMITTED WERE REVIEWED BY SOMEONE OTHER THAN |
| ARCHITECT OF RECORD. PER BUILDING OFFICIAL, A DESIGN |
| PROFESSIONAL OTHER THAN THE ARCHITECT OF RECORD BUT |
| FROM THE SAME OFFICE MAY REVIEW ON BEHALF OF THE |
| ARCHITECT OF RECORD. THAT LICENSED INDIVIDUAL IS TO |
| INCLUDE THEIR FULL NAME AND LICENSE NUMBER ON THE |
| REVIEW STAMP. |
| |
| THE 3100 RESISTOR STOREFRONT IS REFERENCED ON SHEET |
| A1.1.1, BUT I WAS UNABLE TO LOCATE A REFERENCE TO THE |
| DOOR. EITHER HAVE ARCHITECT SIGN THE SHOP DRAWING |
| REVIEW STAMP FOR THE DOOR, OR INCORPORATE A REFERENCE |
| IN THE PLAN. FYI, IF ARCHITECT?S REVIEW IS DONE VIA A |
| REFERENCE IN THE PLAN, A CHANGE OF PRODUCT WOULD |
| REQUIRE A REVISION TO THE PLAN AS WELL AS A NEW PRODUCT |
| APPROVAL TO BE SUBMITTED. |
| |
| 24. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS |
| COMPLIANCE WITH FBC ACCESSIBILITY 405.7, LANDINGS AT |
| THE TOP AND BOTTOM OF THE RAMP. |
| |
| 25. PROVIDE A DETAIL FOR THE RAMP WHICH SHOWS |
| COMPLIANCE WITH FBC ACCESSIBILITY 405.6, RAMP RISE NOT |
| TO EXCEED 30 INCHES. A SECTION IS SUGGESTED. |
| |
| 26. A2.01, DETAIL A, SHOWS A RAIN LEADER AND HOSE BIBB |
| AT THE BOTTOM OF THE RAMP. EITHER REVISE TO A DIFFERENT |
| LOCATION OR PROVIDE A DETAIL TO SHOW HOW THIS WILL NOT |
| AFFECT THE WALKING SURFACE STABILITY FBC ACCESSIBILITY |
| 302.1 AND HOW THIS WILL NOT PROTRUDE INTO THE MEANS OF |
| EGRESS. |
| |
| 27. A2.02, COUNTERTOP HEIGHT NOT CLEAR. DETAIL A SHOWS |
| A DIMENSION OF 2 FT FOR COUNTER BAR TOP, BUT THE NOTE |
| SPECS 42 INCHES. |
| |
| REVISE PLAN TO SHOW SEATING AREAS AND SHOW COMPLIANCE |
| WITH FBC ACCESSIBILITY 902. |
| |
| 28. FBC ACCESSIBILITY, REVISE PLAN TO SHOW LOCATION OF |
| CHECK OUT AISLES, SALES AND SERVICE COUNTERS, FBC |
| ACCESSIBILITY 904. |
| . A2.02 DETAIL 5 DEPICTS A WALL WITH WINDOWS AND DOORS, |
| CLARIFY LOCATION. |
| |
| 29. PROVIDE A DETAIL FOR THE MEANS OF EGRESS STAIR FROM |
| THE FRONT PATIO TO REAR OF BUILDING, FBC 107. S2.0 |
| APPEARS TO SHOW THIS AS EXISTING, A1.1.1 SPECS STEEL |
| STAIRS. |
| |
| 30. WHEN A CONTRACTOR IS ASSIGNED, PROVIDE A COPY OF |
| THE CONTRACT FOR THIS JOB, FBC 109. THE VALUE ON THE |
| PERMIT APPLICATION IS TO INCLUDE LABOR, MATERIALS, |
| OVERHEAD, PROFIT, EVEN IF PROVIDED BY OTHERS. |
| |
| THIS ITEM SHOULD NOT DELAY RESUBMITTAL (MAY BE DEALT |
| WITH AT A LATER DATE, PRIOR TO ISSUANCE). |
| |
| |