2017-05-11 13:35:27 | 3RD REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A3.01 THE NOTE ON OVERFLOW SCUPPER STATES THAT |
| IT IS TO CONNECT TO THE CATCH BASIN THE OVER FLOW DRAIN |
| SHALL TERMINATE ABOVE GRADE AND WHERE THE BUILDING |
| OCCUPANTS CAN OBSERVE IT . PER FBC PL 1108.2 SEPARATE |
| SYSTEMS REQUIRED. |
| SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT |
| OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM. |
| DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT |
| WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| MAINTENANCE PERSONNEL. |
| |
| 2. SHT. A8.04 DETAIL #8 THE EMERGENCY SCUPPER SHALL BE |
| A MIN OF 2" ABOVE THE ROOF. PER FBC |
| 1503.4.2.1 OVERFLOW SCUPPERS. |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| SCUPPERS |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |