2017-04-20 14:40:281ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090622
 4/20/17
  
 1) COMMENT #6 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS. A) THE WIND LOAD DESIGN CRITERIA HAS NOT BEEN
 PROVIDED AS REQUESTED. B) THE ERV DETAIL ON M3.2 DOES
 NOT PROVIDE INSTALLATION DETAILS, NOR DOES IT PROVIDE A
 REFERENCE NOTE TO INDICATE WHERE THE DETAILS ARE. IT
 WOULD BE HELPFUL FOR REVIEW, INSTALLATION, AND
 INSPECTION PURPOSES TO RELOCATE THE DETAIL FROM SHEET
 A8.04 TO M3.2.
 C) THE NOA FOR THE ROOF STAND MUST HAVE THE APPLICABLE
 STAND CONFIGURATIONS, INSTALLATION DETAILS, DESIGN
 PRESSURES ETC. EITHER CIRCLED, HIGHLIGHTED, OR
 OTHERWISE MARKED BY ENGINEER OF RECORD.
  
 2) A REVIEW OF THE AC HEATING CALCULATIONS FOR THE
 SYSTEMS INDICATES THE HEAT STRIPS HAVE BEEN OVERSIZED-
 SEE SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER