2016-09-27 08:42:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090622
 9/27/16
  
 1) PROVIDE THE AC EQUIPMENT SCHEDULES ON THE PLANS FOR
 ALL OF THE FUTURE AC SYSTEMS SHOWN ON THE PLANS AND IN
 THE CALCULATIONS.
  
 2) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE ART
 STUDIOS AND INDICATE ON THE PLAN HOW COMPLIANCE WILL BE
 MET- TABLE 6-4 ASHRAE 62.1-2010, TABLE 403.3 FBC-14
 MECHANICAL (SEE FOOTNOTE G).
  
 3) SHEET M1.1: THE CORRIDOR CANNOT BE USED TO CONVEY
 RETURN AIR- SECTION 601.2
  
 4) M1.1: PROVIDE A SHUTOFF DAMPER FOR THE O/A DUCT TO
 AHU-1 PER SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 5) M1.1; PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1-
 SHOW THE PIPING RUN AND DISCHARGE LOCATION- SECTION
 307.
  
 6) M1.1: PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 STRUCTURAL DETAILS FOR ANCHORING THE ERV AND CURB TO
 THE ROOF STRUCTURE- SECTION 301.15. PROVIDE TWO COPIES
 OF MIAMI-DADE ROOF STAND NOA #16-0601.01 WITH APPROVAL
 SIGNATURE AND ALL APPLICABLE INSTALLATION DETAILS AND
 NOTES MARKED BY THE EOR. ( PLEASE NOTE NOA #15-0902.05
 SPECIFIED ON M3.2 HAS BEEN SUPERCEDED).
  