2016-09-26 08:30:10 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| WIRELESS SYSTEM, ETC. A NOTE WILL SUFFICE. |
| 2. PLEASE ADD A GENERAL NOTE TO SHEETS TO INDICATE THE |
| REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM |
| COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A |
| WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN |
| FOR THIS PROJECT. A NOTE WILL SUFFICE |
| 3. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY |
| REGULATORY AGENCIES. |
| 4. PLEASE PROVIDE AVAILABLE FAULT CURRENT AVAILABLE AT |
| THE FPL SERVICE. ATTACH TO DOCUMENTS LETTER FROM |
| FLORIDA POWER & LIGHT INDICATING AIC. SHOW AIC |
| CALCULATION BASED ON INFORMATION PROVIDED BY UTILITY |
| FOR APPROVAL. NEC 110.24 FBC 107 |
| 5. PROVIDE LIGHTING DENSITIES PER FLORIDA BUILDING CODE |
| ENERGY CONSERVATION 2014 5TH EDITION |
| 6. PLEASE ADDRESS FIRE COMMENTS RELATED TO THE |
| ELECTRICAL SCOPE OF WORK. |
| 7. CLARIFY IF THIS IS A SHELL PERMIT, ITEMS MARKED AS |
| FUTURE INSTALL (SUBJECT TO BUILDING REVIEW)? |
| 8. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE |
| PER NEC 250.94 |
| 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| THIS PROJECT. |
| |
| |
| VALENTINO PEREZ |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6717 |