1 |
|
Notes |
Date |
Text |
2016-09-28 16:08:06 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] PROVIDE A PROPOSED SIGN ELECTRICAL DETAIL TO INCLUDE | | THE FOLLOWING : | | | | 1A] NEC 600.5 A MINIMUM 20 AMP DEDICATED BRANCH CIRCUIT | | ( IF EXISTING PLEASE MARK ON PLANS ) | | | | 1B] NEC 600.6 PROVIDE A DISCONNECT EITHER WITHIN-SIGHT | | OR AS AN INTERGAL PART OF THE SIGN. | | | | 1C] NEC 600.7 SHOW AN EQUIPMENT GROUNDING CONDUCTOR | | ROUTED ALONG WITH THE SUPPLY BRANCH CIRCUIT FOR THE | | SIGN BONDING CONNECTIONS. | | | | 2] FBC-E_C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING | | NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND | | A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING | | DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE | | CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | PHOTOSENSOR. | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. | | | | 3] PROVIDE AN OWNER SIGNED CONTRACT BECAUSE VALUE SEEMS | | TO BE TOO LOW FBC-109 |
|