Plan Review Notes
Plan Review Notes For Permit 16090609
Permit Number 16090609
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-28 16:08:06REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PROVIDE A PROPOSED SIGN ELECTRICAL DETAIL TO INCLUDE
 THE FOLLOWING :
  
 1A] NEC 600.5 A MINIMUM 20 AMP DEDICATED BRANCH CIRCUIT
 ( IF EXISTING PLEASE MARK ON PLANS )
  
 1B] NEC 600.6 PROVIDE A DISCONNECT EITHER WITHIN-SIGHT
 OR AS AN INTERGAL PART OF THE SIGN.
  
 1C] NEC 600.7 SHOW AN EQUIPMENT GROUNDING CONDUCTOR
 ROUTED ALONG WITH THE SUPPLY BRANCH CIRCUIT FOR THE
 SIGN BONDING CONNECTIONS.
  
 2] FBC-E_C405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING
 NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
  
 3] PROVIDE AN OWNER SIGNED CONTRACT BECAUSE VALUE SEEMS
 TO BE TOO LOW FBC-109