2016-10-15 05:05:07 | 1) SHT. P413 - THE ADDED OUTDDOOR KITCHEN IS NOT SHOWN |
| ON THE SANITARY RISER DIAGRAM BUT IS SHOWN ON SHTS.P100 |
| C & P101 C CLARIFY. |
| 2) EXPLAIN WHAT PROCESS IS TAKING PLACE AT THE "OUTDOOR |
| KITCHEN." THE WASTE FROM THIS AREA MAY BE REQUIRED TO |
| DISCHARGE TO THE GREASY WASTE. THE PLUMBING DRAWINGS DO |
| NOT SHOW WHERE THE DRAINAGE LINE FOR THIS AREA CONNECTS |
| OR WHAT TYPE OF WASTE IS DISCHARGING INTO THIS LINE. |
| 3) SHT. P413. THE DRAIN LINE FOR THE POOL STORAGE ROOM |
| AND THE DRINKING FOUNTAINS IS NOT SHOWN ON THE GRAVITY |
| RISER DIAGRAM BUT IS SHOWN ON SHTS. P100 C & 101 C. |
| CLARIFY. |
| 4) SHT. P100 C REFERS TO SHT. P100 B FOR MATCLINE. |
| THERE IS NO SHT. P100 B IN THIS SET. CLARIFY. |
| 5) SHT. P101 B - DELTA 22 DATED 9/16/16 - INDICATES |
| THIS CHANGE RELATES TO BULLETIN NO. 10 YET THE OTHER |
| SHEETS NOTE THAT DELTA 22 RELATES TO BULLETIN #22. THE |
| SAME THING OCCURS ON SHT. P 103 A AND DELTA 22 IS NOT |
| EVEN LISTED ON SHT. P104 A. PLEASE CLARIFY AS THIS IS |
| VERY CONFUSING IN MAKING A DETRMINATION AS TO WHAT |
| CHANGES AND WHERE HAVE BEEN MADE TO THE PLANS. |
| 6) SHT. P 201 C - INDICATES A CHANGE HAS BEEN MADE TO |
| THIS SHEET BUT IT IS NOT LISTED IN THE NARRATIVE UNDER |
| BULLETIN NO. 22. CLARIFY. |
| 7) SHTS. P 210 A & P210 B - SHOW THE ADDED HOT WATER |
| RECIRCULATION LINE BY CLOUDING AND THE DELTA NUMBER. |
| WPB AMEND TO FBC SEC. 107.2.1. |
| 8) SHT. P 402 - DELTA 22 DATED 9/16/16 - INDICATES THIS |
| CHANGE RELATES TO BULLETIN NO. 10 YET THE OTHER SHEETS |
| NOTE THAT DELTA 22 RELATES TO BULLETIN #22. PLEASE |
| CLARIFY AS THIS IS VERY CONFUSING IN MAKING A |
| DETRMINATION AS TO WHAT CHANGES AND WHERE HAVE BEEN |
| MADE TO THE PLANS. |
| 9) SHT. P413 - WC-3 OF THE 4 INCH BUILDING DRAIN |
| REQUIRES AN INDIVIDUAL VENT. AS DRAWN, IT DOES NOT |
| COMPLY WITH FPC SEC.909.1 FOR FIXTURES PERMITTED ON A |
| WET VENT. THE WRONG WATER CLOSET WAS GIVEN A VENT. SEE |
| WC-3 IN TOILET ROOM #168. |
| |