2016-10-03 13:23:531) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/
 DRYER SHALL BE PROVIDED WITH ACCESS PER 2010 FPC
 SEC.606.3.
 2) SHT. P101A - THE NOTES ON THE RIGHT SIDE OF THE PLAN
 ARE COVERED BY THE DESIGN TEAM NAMES. PROVIDE A SHEET
 WHERE THE NOTES ARE VISIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THE DESCRIPTION OF THE PLUMBING CHANGES IN THE
 NARRATIVE IS VERY VAGUE. PLEASE PROVIDE A CLEAR
 DESCRIPTION OF THE CHANGES MADE TO THE PLUMBING SYSTEM
 ON THE APPLICABLE SHEETS. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) ALL OB-1 FIXTURES ON THE RISERS SHALL DISCHARGE INTO
 A 3 INCH STACK PER 2010 FPC SEC.406.3.
 5) SHT. P403 - RISERS #7,8,9,11,12 & 15 FOR THE FIRST
 AND SECOND FLOORS APPEAR TO HAVE FLAT, DRY VENTS
 CONNECTED TO THE STACKS. IF CONNECTED AT A 45 DEGREE
 ANGLE, IT WOULD COMPLY WITH THE PLUMBING CODE. A NOTE
 CAN BE PLACED ON THE PLANS STATING THE VENTS ARE
 CONNECTED AT A 45DEGREE ANGLE.
 6) SHT. P403 - THE WASHING MACHINE ON RISER #12 CANNOT
 DISCHARGE INTO A WET VENT PERR SEC.909.1 OF 2010 FPC. A
 VENT ON THE BATHTUB WILL CORRECT THIS ISSUE.
 7) SHT. P413 - WC-3 OF THE 4 INCH BULDDING DRAIN
 REQUIRES AN INDIVIDUAL VENT. AS DRAWN, IT DOES NOT
 COMPLY WITH FPC SEC.909.1 FOR FIXTURES PERMITTED ON A
 WET VENT.
  