Plan Review Notes For Permit 16090593 |
Permit Number |
16090593 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-03 13:23:53 | 1) THE WATER SUPPLY VALVES FOR THE STACKED WASHER/ | | DRYER SHALL BE PROVIDED WITH ACCESS PER 2010 FPC | | SEC.606.3. | | 2) SHT. P101A - THE NOTES ON THE RIGHT SIDE OF THE PLAN | | ARE COVERED BY THE DESIGN TEAM NAMES. PROVIDE A SHEET | | WHERE THE NOTES ARE VISIBLE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 3) THE DESCRIPTION OF THE PLUMBING CHANGES IN THE | | NARRATIVE IS VERY VAGUE. PLEASE PROVIDE A CLEAR | | DESCRIPTION OF THE CHANGES MADE TO THE PLUMBING SYSTEM | | ON THE APPLICABLE SHEETS. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 4) ALL OB-1 FIXTURES ON THE RISERS SHALL DISCHARGE INTO | | A 3 INCH STACK PER 2010 FPC SEC.406.3. | | 5) SHT. P403 - RISERS #7,8,9,11,12 & 15 FOR THE FIRST | | AND SECOND FLOORS APPEAR TO HAVE FLAT, DRY VENTS | | CONNECTED TO THE STACKS. IF CONNECTED AT A 45 DEGREE | | ANGLE, IT WOULD COMPLY WITH THE PLUMBING CODE. A NOTE | | CAN BE PLACED ON THE PLANS STATING THE VENTS ARE | | CONNECTED AT A 45DEGREE ANGLE. | | 6) SHT. P403 - THE WASHING MACHINE ON RISER #12 CANNOT | | DISCHARGE INTO A WET VENT PERR SEC.909.1 OF 2010 FPC. A | | VENT ON THE BATHTUB WILL CORRECT THIS ISSUE. | | 7) SHT. P413 - WC-3 OF THE 4 INCH BULDDING DRAIN | | REQUIRES AN INDIVIDUAL VENT. AS DRAWN, IT DOES NOT | | COMPLY WITH FPC SEC.909.1 FOR FIXTURES PERMITTED ON A | | WET VENT. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|