Plan Review Notes For Permit 16090562 |
Permit Number |
16090562 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-20 16:28:32 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16090562 | | 9/20/16 | | | | 1) PLEASE PROVIDE ADDITIONAL INFORMATION CONCERNING THE | | RELOCATED GRILL: A) MAKE AND MODEL. B) TYPE OF FUEL. C) | | IS THERE AN EXISTING EXHAUST HOOD BEING RELOCATED WITH | | IT? | | | | 2) PROVIDE THE WIND LOAD DESIGN CRITERIA FOR THE | | ROOFTOP CONDENSER AND STAND INSTALLATIONS- SECTION | | 301.15 FBC-14 MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|