Plan Review Notes
Plan Review Notes For Permit 16090562
Permit Number 16090562
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-09-23 15:16:02600 OKEECHOBEE BOULEVARD
 PERMIT #16090562
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE NEW HOLLOW METAL DOOR TO THE FAR WEST OPENS INTO
 AND OBSTRUCTS THE SIDEWALK EGRESS PATH OF THE POOL
 DECK. I BELIEVE THE ORIGINAL LIFE SAFETY PLAN INDICATED
 AN OCCUPANT LOAD OF 300-400 UTILIZING THIS EGRESS PATH
 BETWEEN THE HOTEL AND CONVENTION CENTER.
  
 THE GRILL IS LOCATED CLOSER THAN 10 FEET TO THE
 BUILDING AND THE NEW ROOF TRELLIS. PER NFPA 1 SECTION
 10.11.6 COOKING EQUIPMENT: NO HIBACHI, GRILL, OR OTHER
 SIMILAR DEVICES USED FOR COOKING, HEATING, OR ANY OTHER
 PURPOSE SHALL BE USED OR KINDLED ON ANY BALCONY, UNDER
 ANY OVERHANGING PORTION, OR WITHIN 10 FEET OF ANY
 STRUCTURE. RELOCATE OR PROTECT THE GRILL IN ACCORDANCE
 WITH NFPA 96 - STANDARD FOR VENTILATION CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  