2016-10-17 14:28:55 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16090562 |
| ADD: 600 OKEECHOBEE BLVD./RENOVATION SOUTH POOL BAR |
| CONT: HEDRICK BROTHERS |
| TEL: 561-267-1309 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. OCT. 17/2016 |
| ACTION: DENIED |
| |
| |
| 1) SHEET S0.1 INDICATES PRESSURES FOR THIS BUILDING. |
| THERE IS A TABLE FOR COMPONENTS AND CLADDING FOR |
| PRESSURES FOR BUILDINGS GREATER THAN 60 FT. THE TABLE |
| ITSELF IS NOT IDENTIFIED? THE DESIGN CRITERIA INDICATES |
| ASCE 710 170 VULT/ EXPOSURE D. PLEASE NOTE THE |
| PRESSURES ARE LOW WHEN COMPARED TO ASCE 7-10 TABLE |
| 30.7.2 COMPONENTS AND CLADDING PART 4 / V= 160-200 MPH/ |
| VULT/ H=90-160. PLEASE NOTE THE PROVIDED PRESSURES ARE |
| EVEN LOWER THAN THE PRESSURES PREFORMED IN THE WIND |
| TUNNEL TESTING FOR THIS BUILDING. |
| |
| 2) PROVIDE COMPLIANCE WITH / 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) DOORS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) SHEET M1.0 SHOWS A NEW A/C STAND PLEASE PROVIDE |
| COMPLIANCE WHEN SUBMITTING THE ROOF TOP STAND PRODUCT |
| APPROVAL, PLEASE IDENTIFY THE CALCULATION OF THE AREA |
| OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF HEIGHT OF |
| THE STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| PARAMETERS IN THE TABLES , ANCHORS AND UPLIFT VERSES |
| MOMENT. |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 5) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 1509.6.4 |
| EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING |
| ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT |
| A HEIGHT EXCEEDING 16 FEET), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES HIGH. |
| |
| 6) THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER WELD OPERATOR PERFORMANCE |
| QUALIFIACTION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARD. 2014 FBC-B 2204.1 WELDING. THE DETAILS OF |
| DESIGN, WORKMANSHIP AND TECHNIQUE FOR WELDING, |
| INSPECTION OF WELDING AND QUALIFICATION OF WELDING |
| OPERATORS SHALL CONFORM TO THE REQUIREMENTS OF THE |
| SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207, |
| 2210 AND 2211. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |