Plan Review Notes
Plan Review Notes For Permit 16090562
Permit Number 16090562
Review Stop B
Sequence Number 1
Notes
Date Text
2016-10-17 14:28:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090562
 ADD: 600 OKEECHOBEE BLVD./RENOVATION SOUTH POOL BAR
 CONT: HEDRICK BROTHERS
 TEL: 561-267-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 17/2016
 ACTION: DENIED
  
  
 1) SHEET S0.1 INDICATES PRESSURES FOR THIS BUILDING.
 THERE IS A TABLE FOR COMPONENTS AND CLADDING FOR
 PRESSURES FOR BUILDINGS GREATER THAN 60 FT. THE TABLE
 ITSELF IS NOT IDENTIFIED? THE DESIGN CRITERIA INDICATES
 ASCE 710 170 VULT/ EXPOSURE D. PLEASE NOTE THE
 PRESSURES ARE LOW WHEN COMPARED TO ASCE 7-10 TABLE
 30.7.2 COMPONENTS AND CLADDING PART 4 / V= 160-200 MPH/
 VULT/ H=90-160. PLEASE NOTE THE PROVIDED PRESSURES ARE
 EVEN LOWER THAN THE PRESSURES PREFORMED IN THE WIND
 TUNNEL TESTING FOR THIS BUILDING.
  
 2) PROVIDE COMPLIANCE WITH / 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) DOORS
 (G) PRE-ENGINEERED A/C STANDS
  
 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) SHEET M1.0 SHOWS A NEW A/C STAND PLEASE PROVIDE
 COMPLIANCE WHEN SUBMITTING THE ROOF TOP STAND PRODUCT
 APPROVAL, PLEASE IDENTIFY THE CALCULATION OF THE AREA
 OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF HEIGHT OF
 THE STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES , ANCHORS AND UPLIFT VERSES
 MOMENT.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 5) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 1509.6.4
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH.
  
 6) THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER WELD OPERATOR PERFORMANCE
 QUALIFIACTION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARD. 2014 FBC-B 2204.1 WELDING. THE DETAILS OF
 DESIGN, WORKMANSHIP AND TECHNIQUE FOR WELDING,
 INSPECTION OF WELDING AND QUALIFICATION OF WELDING
 OPERATORS SHALL CONFORM TO THE REQUIREMENTS OF THE
 SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207,
 2210 AND 2211.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  