Plan Review Notes For Permit 16090560 |
Permit Number |
16090560 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-06-12 09:14:41 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16090560 | | 6/12/17 | | | | 1) THE DWLK EXHAUST DUCT MUST BE INSTALLED IN A | | FIRE-RATED ENCLOSURE FROM THE POINT IT PENTRATES THE | | CEILING, AND PASSES THROUGH THE ABOVE-CEILING SPACE TO | | THE EXTERIOR WALL- PLEASE SEE PAGE 5 OF THE SUBMITTED | | MARRA FORNI FACTORY DUCT SPECIFICATIONS. IT IS ALSO | | IMPORTANT TO NOTE THAT, PER THE SPECS, THE DUCT | | WRAPPING CANNOT BE INSTALLED TO REDUCE CLEARANCES OR TO | | CREATE SOME TYPE | | | | OF FIRE PROTECTIVE ENCLOSURE. | | | | 2) CLEANOUTS FOR THE TWO EXHAUST DUCTS MUST BE LOCATED | | AT THE CHANGES OF DIRECTION ABOVE THE DRYWALL CEILING | | WHICH WILL REQUIRE THE INSTALLATION OF ACCESS PANELS- | | SEE PAGE 5 OF THE SPECS AND SECTION 506.3.9 FBC-14 | | MECHANICAL. SHOW WHERE THE PANELS WILL BE LOCATED AND | | PROVIDE DETAILS. | | | | 3) ADVISORY: THE SUBMITTED SPECS FOR THE GRILLWORKS | | WOOD-FIRED GRILL INDICATE THE APPLIANCE IS NOT | | CURRENTLY UL 2162 LISTED AND LABELED AS REQUIRED BY | | SECTION 917.1- SEE PAGE 5 OF THE INSTALLATION | | INSTRUCTIONS. IF CHOOSING TO INSTALL THE APPLIANCE | | PLEASE NOTE THAT A THIRD PARTY TESTING SERVICE MUST BE | | EMPLOYED TO PROVIDE FIELD TESTING AND LABELING. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|