Plan Review Notes
Plan Review Notes For Permit 16090560
Permit Number 16090560
Review Stop M
Sequence Number 3
Notes
Date Text
2017-06-12 09:14:413RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16090560
 6/12/17
  
 1) THE DWLK EXHAUST DUCT MUST BE INSTALLED IN A
 FIRE-RATED ENCLOSURE FROM THE POINT IT PENTRATES THE
 CEILING, AND PASSES THROUGH THE ABOVE-CEILING SPACE TO
 THE EXTERIOR WALL- PLEASE SEE PAGE 5 OF THE SUBMITTED
 MARRA FORNI FACTORY DUCT SPECIFICATIONS. IT IS ALSO
 IMPORTANT TO NOTE THAT, PER THE SPECS, THE DUCT
 WRAPPING CANNOT BE INSTALLED TO REDUCE CLEARANCES OR TO
 CREATE SOME TYPE
  
 OF FIRE PROTECTIVE ENCLOSURE.
  
 2) CLEANOUTS FOR THE TWO EXHAUST DUCTS MUST BE LOCATED
 AT THE CHANGES OF DIRECTION ABOVE THE DRYWALL CEILING
 WHICH WILL REQUIRE THE INSTALLATION OF ACCESS PANELS-
 SEE PAGE 5 OF THE SPECS AND SECTION 506.3.9 FBC-14
 MECHANICAL. SHOW WHERE THE PANELS WILL BE LOCATED AND
 PROVIDE DETAILS.
  
 3) ADVISORY: THE SUBMITTED SPECS FOR THE GRILLWORKS
 WOOD-FIRED GRILL INDICATE THE APPLIANCE IS NOT
 CURRENTLY UL 2162 LISTED AND LABELED AS REQUIRED BY
 SECTION 917.1- SEE PAGE 5 OF THE INSTALLATION
 INSTRUCTIONS. IF CHOOSING TO INSTALL THE APPLIANCE
 PLEASE NOTE THAT A THIRD PARTY TESTING SERVICE MUST BE
 EMPLOYED TO PROVIDE FIELD TESTING AND LABELING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  