Plan Review Notes For Permit 16090560 |
Permit Number |
16090560 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-05-22 15:47:30 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16090560 | | 5/22/17 | | | | 1) SHEET M1.1: IT APPEARS THAT THE DISCHARGE OUTLETS | | FOR EXHAUST FANS KEF-1 & 2 ARE LESS THAN THE REQUIRED | | 10' CLEARANCE DISTANCE TO THE BUILDING AND POARAPET | | WALLS- SEE SECTION 506.3.13.3 AND RELOCATE THE FANS. | | | | 2) SUBMIT A PRODUCT DATA SHEET FOR THE DWKL PIZZA OVEN | | EXHAUST DUCT THAT VERIFIES THE DUCT IS UL 2221 LISTED | | AND LABELED AS A GREASE ENCLOSURE- SECTION 506.3.11.3. | | | | 3) AS PREVIOUSLY REQUESTED THE NEWFINISHED BUILDING | | CLASSIFICATION SHOWN IN THE ENERGYGAUGE PROJECT SUMMARY | | MUST BE CHANGED TO ADDITION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|