Plan Review Notes
Plan Review Notes For Permit 16090560
Permit Number 16090560
Review Stop B
Sequence Number 2
Notes
Date Text
2017-05-30 07:20:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16090560
 ADD: 600 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-267-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES.MAY 30/2017
 ACTION: DENIED
  
 1) 2ND REOUND COMMENTS. SHEET S0.1 THE TABLE OF
 PRESSURES IS STILL LOW, THE BUILDING HEIGHT FOR THE
 PRESSURES IS NOT GIVEN. THE PRESSURES FROM WHEN THE
 BUILDING WAS BUILT ARE OVER 1.5 PSF THE PRESSURES GIVEN
 IN THIS REVIEW. ENG. FRANK BENNARDOS PRESSURES ARE
 ONLY0.3 PSF HIGHER THAN THE GIVEN PRESSURES UNDER WHICH
 THE BUILDING WAS BUILT FOR 140 FEET IN ELEVATION. THE
 2ND DIFFERENCE IN THE ORIGINAL BUILDING DESIGN THE EDGE
 STRIP AND CORNER STRIP WAS 24 FEET, NOT THE 22 FEET
 INDICATED IN THIS REVIEW. PLEASE PROVIDE HOW THE
 PRESSURES AND EDGE AND CORNER STRIP CAN VERY SO MUCH TO
 (2) OTHER ENGINEERS FOR THE SAME BUILDING?
  
 1ST ROUND OF COMMENTS. SHEET S0.1 INDICATES PRESSURES
 FOR THIS BUILDING. THERE IS A TABLE FOR COMPONENTS AND
 CLADDING FOR PRESSURES FOR BUILDINGS GREATER THAN 60
 FT. THE TABLE ITSELF IS NOT IDENTIFIED? THE DESIGN
 CRITERIA INDICATES ASCE 710 170 VULT/ EXPOSURE D.
 PLEASE NOTE THE PRESSURES ARE LOW WHEN COMPARED TO ASCE
 7-10 TABLE 30.7.2 COMPONENTS AND CLADDING PART 4 / V=
 160-200 MPH/ VULT/ H=90-160. PLEASE NOTE THE PROVIDED
 PRESSURES ARE EVEN LOWER THAN THE PRESSURES PREFORMED
 IN THE WIND TUNNEL TESTING FOR THIS BUILDING.
  
 2) BUILDING PROVISO: PROVIDE COMPLIANCE WITH / 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 D) ROOFING PRODUCTS AND ASSEMBLIES/ INSULATION/ ROOF
 TOP FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 3)BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4)2ND REQUEST. NANA WALL NOA 15-0226.05 SHEET 7 OF 8
 ADA SILL DETAIL INDICATES WHEN AN ADA/ FLUSH SADDLE IS
 USED, THESE DOORS ARE NOT APPROVED FOR USE WHERE WATER
 INFILTRATION RESISTANCE IS REQUIRED BY THESE DOORS
 UNLESS UNITS ARE INSTALLED IN NON-HABITABLE AREAS WHERE
 THE UNITS AND THE AREAS ARE DESIGNED TO ACCEPT WATER
 INFILTRATION OR THEY ARE INSTALLED ONLY AT LOCATIONS
 PROTECTED BY A CANOPY OR OVERHANG WHERE BY THE OVERHANG
 (OH) RATIO IS EQUAL TO OR MORE THAN 1.0 PER FBC.
  
 1ST ROUND OF COMMENTS. THE NANA WALL SYSTEM PLEASE
 PROVIDE THE HEIGHT OF THE BOTTOM TRACK AND WILL THE
 BOTTOM TRACK BE IN COMPLIANCE WITH BOTH ACCESSIBILITY
 AND THE REQUIRED PRESSURES FOR THIS BUILDING? ACCESS.
 CODE 404.3.3 THRESHOLDS. THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 404.2.5. 404.2.5
 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
 EXCEPTION: EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19
 MM) HIGH MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE
 WITH A SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED
 TO COMPLY WITH 404.2.5.
  
 5)BUILDING PROVISO: SHEET A1.1 SHOWS A NEW A/C STAND
 PLEASE PROVIDE COMPLIANCE WHEN SUBMITTING THE ROOF TOP
 STAND PRODUCT APPROVAL, PLEASE IDENTIFY THE CALCULATION
 OF THE AREA OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES , ANCHORS AND
 UPLIFT VERSES MOMENT.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) COMPLIED. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B
 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES HIGH.
  
 7) BUILING PROVISO: THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER WELD
 OPERATOR PERFORMANCE QUALIFIACTION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARD. 2014 FBC-B
 2204.1 WELDING. THE DETAILS OF DESIGN, WORKMANSHIP AND
 TECHNIQUE FOR WELDING, INSPECTION OF WELDING AND
 QUALIFICATION OF WELDING OPERATORS SHALL CONFORM TO THE
 REQUIREMENTS OF THE SPECIFICATIONS LISTED IN SECTIONS
 2205, 2206, 2207, 2210 AND 2211.
  
 8)SEMI-COMPLIED. THE LIFESAFETY SHEET LS1.0 SHOWS THE
 TABLE AND CHAIR LAYOUT INSIDE, NO SEATING IS SHOWN ON
 THE EXTERIOR OF THE BUILDING, PLEASE PROVIDE COMPLIANCE
 WITH THE 2014 FL. ACCESSIBILITY CODE:
  
 8A) 2ND REQUEST. THE OUTSIDE SEATING AREA HAS 78 SEATS.
 78 X 0.05= 3.9 OR 4 ACCESSIBLE SEATS NEED TO BE SHOWN
 ON THE PLAN. THE PLAN ONLY SHOWS 3 OUTDOOR SEATS.
  
 1ST ROUND OF COMMENT. 226.1WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 8B) 226.2 DISPERSION. DINING SURFACES REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES.
  
 8C) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 8D) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 9) 2ND REQUEST. APPROXIMATELY 488 SQUARE FEET OF
 INTERIOR A/C AREA IS BEING ADDED TO THE BUILDING, MAY
 REQUIRE IMPACT FEE ASSESSMENT.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  