2016-09-22 10:39:30 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| ENERGY CONSERVATION CODES |
| PERMIT #16090560 |
| 9/22/16 |
| |
| 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| AND PROVIDE A O/A VENTILATION CALCULATION FOR THE |
| EXPANDED DINING ROOM AND KITCHEN AREA PER TABLE 403.3 |
| FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES |
| THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 2) THE SUBMITTED AC CALCULATIONS INDICATE 100 CFMS OF |
| OUTDOOR VENTILATION AIR. PLEASE CLARIFY HOW THE AIR IS |
| BEING PROVIDED TO THE AHU'S- NO O/A DUCTS ARE SHOWN. |
| |
| 3) THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM INDICATES |
| "NEW FINISHED BUILDING" ON PAGE 2. THE PLANS ARE |
| INDICATING AN EXTENSION OF CONDITIONED SPACE WHICH IS |
| DEFINED AS AN ADDITION- SEE SECTION 202 FBC-14 ENERGY |
| CONSERVATION. PLEASE CORRECT THE CALCS. |
| |
| 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING SEPARATE |
| PLANS AND PERMITS ARE REQUIRED FOR THE NEW EXHAUST |
| HOODS AND FIRE SUPPRESSION SYSTEMS. PLEASE NOTE THAT |
| THE REQUIREMENT FOR MAKEUP AIR TEMPERATURE WILL BE |
| REVIEWED UNDER THAT PERMIT- REFER TO SECTION 508.1.1. |
| |
| 5) STRUCTURAL DETAILS AND WIND LOAD DESIGN CRITERIA FOR |
| INSTALLATION OF THE ROOF TOP MECHANICAL EQUIPMENT NOT |
| PROVIDED- SECTION 301.15. |
| |