2016-09-22 10:39:301ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16090560
 9/22/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE A O/A VENTILATION CALCULATION FOR THE
 EXPANDED DINING ROOM AND KITCHEN AREA PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE SUBMITTED AC CALCULATIONS INDICATE 100 CFMS OF
 OUTDOOR VENTILATION AIR. PLEASE CLARIFY HOW THE AIR IS
 BEING PROVIDED TO THE AHU'S- NO O/A DUCTS ARE SHOWN.
  
 3) THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM INDICATES
 "NEW FINISHED BUILDING" ON PAGE 2. THE PLANS ARE
 INDICATING AN EXTENSION OF CONDITIONED SPACE WHICH IS
 DEFINED AS AN ADDITION- SEE SECTION 202 FBC-14 ENERGY
 CONSERVATION. PLEASE CORRECT THE CALCS.
  
 4) PLEASE PLACE A NOTE ON THE PLANS INDICATING SEPARATE
 PLANS AND PERMITS ARE REQUIRED FOR THE NEW EXHAUST
 HOODS AND FIRE SUPPRESSION SYSTEMS. PLEASE NOTE THAT
 THE REQUIREMENT FOR MAKEUP AIR TEMPERATURE WILL BE
 REVIEWED UNDER THAT PERMIT- REFER TO SECTION 508.1.1.
  
 5) STRUCTURAL DETAILS AND WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP MECHANICAL EQUIPMENT NOT
 PROVIDED- SECTION 301.15.
  