Date |
Text |
2016-10-17 13:38:57 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16090560 |
| ADD: 600 OKEECHOBEE BLVD. |
| CONT: HEDRICK BROTHERS |
| TEL: 561-267-1309 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. OCT. 17/2016 |
| ACTION: DENIED |
| |
| 1) SHEET S0.1 INDICATES PRESSURES FOR THIS BUILDING. |
| THERE IS A TABLE FOR COMPONENTS AND CLADDING FOR |
| PRESSURES FOR BUILDINGS GREATER THAN 60 FT. THE TABLE |
| ITSELF IS NOT IDENTIFIED? THE DESIGN CRITERIA INDICATES |
| ASCE 710 170 VULT/ EXPOSURE D. PLEASE NOTE THE |
| PRESSURES ARE LOW WHEN COMPARED TO ASCE 7-10 TABLE |
| 30.7.2 COMPONENTS AND CLADDING PART 4 / V= 160-200 MPH/ |
| VULT/ H=90-160. PLEASE NOTE THE PROVIDED PRESSURES ARE |
| EVEN LOWER THAN THE PRESSURES PREFORMED IN THE WIND |
| TUNNEL TESTING FOR THIS BUILDING. |
| |
| 2) PROVIDE COMPLIANCE WITH / 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| D) ROOFING PRODUCTS AND ASSEMBLIES/ INSULATION/ ROOF |
| TOP FANS |
| (G) PRE-ENGINEERED A/C STANDS |
| 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 4) THE NANA WALL SYSTEM PLEASE PROVIDE THE HEIGHT OF |
| THE BOTTOM TRACK AND WILL THE BOTTOM TRACK BE IN |
| COMPLIANCE WITH BOTH ACCESSIBILITY AND THE REQUIRED |
| PRESSURES FOR THIS BUILDING? ACCESS. CODE 404.3.3 |
| THRESHOLDS. THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS |
| SHALL COMPLY WITH 404.2.5. 404.2.5 THRESHOLDS. |
| THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303. |
| EXCEPTION: EXISTING OR ALTERED THRESHOLDS 3/4 INCH (19 |
| MM) HIGH MAXIMUM THAT HAVE A BEVELED EDGE ON EACH SIDE |
| WITH A SLOPE NOT STEEPER THAN 1:2 SHALL NOT BE REQUIRED |
| TO COMPLY WITH 404.2.5. |
| |
| 5) SHEET A1.1 SHOWS A NEW A/C STAND PLEASE PROVIDE |
| COMPLIANCE WHEN SUBMITTING THE ROOF TOP STAND PRODUCT |
| APPROVAL, PLEASE IDENTIFY THE CALCULATION OF THE AREA |
| OF THE ROOF TOP COMPRESSORS, THE MEAN ROOF HEIGHT OF |
| THE STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| PARAMETERS IN THE TABLES , ANCHORS AND UPLIFT VERSES |
| MOMENT. |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 6) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 1509.6.4 |
| EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING |
| ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT |
| A HEIGHT EXCEEDING 16 FEET), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES HIGH. |
| |
| 7) THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER WELD OPERATOR PERFORMANCE |
| QUALIFIACTION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARD. 2014 FBC-B 2204.1 WELDING. THE DETAILS OF |
| DESIGN, WORKMANSHIP AND TECHNIQUE FOR WELDING, |
| INSPECTION OF WELDING AND QUALIFICATION OF WELDING |
| OPERATORS SHALL CONFORM TO THE REQUIREMENTS OF THE |
| SPECIFICATIONS LISTED IN SECTIONS 2205, 2206, 2207, |
| 2210 AND 2211. |
| |
| 8) THE LIFESAFETY SHEET LS1.0 SHOWS THE TABLE AND CHAIR |
| LAYOUT INSIDE, NO SEATING IS SHOWN ON THE EXTERIOR OF |
| THE BUILDING, PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| FL. ACCESSIBILITY CODE: |
| |
| 8A) 226.1WHERE DINING SURFACES ARE PROVIDED FOR THE |
| CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| SEATING SPACES AND STANDING SPACES AT THE DINING |
| SURFACES SHALL COMPLY WITH 902. IN ADDITION, WHERE WORK |
| SURFACES ARE PROVIDED FOR USE BY OTHER THAN EMPLOYEES, |
| AT LEAST 5 PERCENT SHALL COMPLY WITH 902. |
| |
| 8B) 226.2 DISPERSION. DINING SURFACES REQUIRED TO |
| COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE |
| OR FACILITY CONTAINING DINING SURFACES. |
| |
| 8C) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 8D) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 9) APPROXIMATELY 488 SQUARE FEET OF INTERIOR A/C AREA |
| IS BEING ADDED TO THE BUILDING, MAY REQUIRE IMPACT FEE |
| ASSESSMENT. |
| BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |