2016-10-03 12:10:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16090546
 10/3/16
  
 1) IT APPEARS THAT THE MAKEUP AIR DUCT INSULATION WRAP
 IS LESS THAN 18" TO BOTH THE GREASE DUCT AND THE
 KITCHEN HOOD: A) PLEASE PROVIDE THE CLEARANCE DISTANCES
 B) PROVIDE A MANUFACTURER'S DATA SHEET FOR THE
 INSULATION INDICATING WHAT THE FACING MATERIAL IS, AND
 THE LIMITATIONS OF USE FOR THE PRODUCT. PLEASE NOTE
 THAT KRAFT OR FOIL FACING WILL BURN AND CANNOT BE LEFT
 EXPOSED.
  
 2) SHOW THE REQUIRED NON-COMBUSTIBLE BACKING MATERIAL
 EXTENDING 18" IN ALL DIRECTIONS ON THE WALL BEHIND THE
 HOOD- SECTION 507.9 EXCEPTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER