Plan Review Notes For Permit 16090546 |
Permit Number |
16090546 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-03 12:10:51 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16090546 | | 10/3/16 | | | | 1) IT APPEARS THAT THE MAKEUP AIR DUCT INSULATION WRAP | | IS LESS THAN 18" TO BOTH THE GREASE DUCT AND THE | | KITCHEN HOOD: A) PLEASE PROVIDE THE CLEARANCE DISTANCES | | B) PROVIDE A MANUFACTURER'S DATA SHEET FOR THE | | INSULATION INDICATING WHAT THE FACING MATERIAL IS, AND | | THE LIMITATIONS OF USE FOR THE PRODUCT. PLEASE NOTE | | THAT KRAFT OR FOIL FACING WILL BURN AND CANNOT BE LEFT | | EXPOSED. | | | | 2) SHOW THE REQUIRED NON-COMBUSTIBLE BACKING MATERIAL | | EXTENDING 18" IN ALL DIRECTIONS ON THE WALL BEHIND THE | | HOOD- SECTION 507.9 EXCEPTION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|