2016-09-16 09:56:04 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| |
| 1. SUBMITTAL IS FOR LAMINATE FLOORING. ASTM SUBMITTED |
| IS FOR QUARRY TILE OVER 8" SLAB. |
| 2. PROVIDE ASTM E 90 (SOUND), ASTM E492 (IMPACT) AND |
| ASTM E84 (FLAME SPREAD) FOR THE PROPOSED LAMINATE |
| FLOORING (NUVELLE VEN 13). |
| |
| FBC 603.1 FLAME SPREAD ? ASTM E-84 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E - 09-02 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| |