2016-09-17 06:02:22 | 1) THIS SUBMITTAL MAKES NO SENSE. THE APPLICATION IS |
| FOR A TANKLESS WATER HEATER AND REPLACING A KITCHEN |
| SINK YET THE ONLY THING SUBMITTED WAS SPEC SHEETS FOR A |
| FIRESTOPPING MORTAR. CLARIFY. |
| |
| 2) SUBMIT A FLOOR PLAN SHOWING WHERE THE WORK IS BEING |
| DONE. |
| |
| 3).SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. |
| G2413. |
| |
| 4).SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING |
| |
| (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO |
| FBC SEC.107.2.1. |
| |
| 5). TYPE OF GAS (LP OR NATURAL). |
| |
| 6). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS |
| SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 |
| (37) OR 2014 FBC-RES. SEC. G2413. |
| |
| 7). SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014 |
| FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G |
| 2413.3. |
| |
| 8). SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 |
| FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| 2407. |
| |
| 9). INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. |
| SEC. G2413.2. . |
| |
| 10). SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS |
| SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426. |
| |
| 11). SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| |
| 12). INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A |
| GAS RISER SHOWING ALL GAS APPLIANCES ON THE SYSTEM, THE |
| BTU LOAD OF EACH APPLIANCE AND THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF EACH SECTION.THE BTU LOAD OF THE |
| EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. FGC SECS. |
| 401.4, 401.8, 402.1,402.2, 402.3 |
| |
| 13) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| |
| 15) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| |
| 16) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE |
| THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC |
| SEC.402.3, FBCR SEC. G 2413.3. |
| |