2016-09-22 07:36:172ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16090453
 9/22/16
  
 1) PROVIDE RETURN AIR FROM BEDROOM #4- SECTION M1602
 FBC-RESIDENTIAL.
  
 2) THE PLAN INDICATES 1180 CFMS AIR DISTRIBUTION AT THE
 TWO TRUNK LINES, BUT ONLY 956 CFMS ARE SHOWN AT THE
 BRANCH DUCTS AND DIFFUSERS- PLEASE CORRECT.
  
 3) WHEN RESUBNITTING OLEASE NOTE TWO SETS OF PLANS ARE
 REQUIRED PER SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  