2016-09-19 17:03:50 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #16090453 |
| 9/19/16 |
| |
| 1) PROVIDE THE AC EQUIPMENT SCHEDULE ON THE PLAN. |
| |
| 2) IDENTIFY ALL ROOMS ON THE PLAN. |
| |
| 3) THE 6" DUCT IS UNDERSIZED FOR 170 CFMS- PLEASE |
| INCREASE THE DUCT SIZE. |
| |
| 4) THE 20"X20" RETURN GRILL AT THE AHU CLOSET IS |
| UNDERSIZED FOR RETURNING 1180 CFMS OF AIR: GRILL SIZE |
| IS TYPICALLY 2 CFMS PER SQ. IN. |
| |
| 5) THE SUBMITTED PLAN HAS NOT BEEN PREPARED OR SIGNED |
| BY THE CONTRACTOR- REFER TO SECTION 107.2 CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE IN |
| ACCORDANCE WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND |
| DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA |
| DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE |
| BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF |
| THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR |
| THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |