Plan Review Notes
Plan Review Notes For Permit 16090445
Permit Number 16090445
Review Stop E
Sequence Number 1
Notes
Date Text
2016-09-22 09:41:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO'S
  
 1] COMPLY WITH OVERHEAD CONDUCTOR CLEARANCES OVER POOLS
 IF THE CONDITIONS EXIST. FBC-R_E4203.6
  
 2] OUTLETS SUPPLYING POOL PUMPS CONNECTED TO 120-240 V
 SINGLE PHASE RATED 15 OR 20 AMP SHALL PROVIDE GFCI
 PROTECTION FOR PERSONNEL. NEC 680.21(C)